Cooper Crouse-Hinds CEAG GUB Serie Instrucciones De Uso página 5

Equipos y cuadros para atmósferas explosivas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Safety instructions
Installation and electrical connections of
equipments and distribution panels may
only be carried out by skilled electricians
and instructed personnel in accordance
with 60079-14 and the respective national
legislation on electrical equipment for
explosive atmospheres.
This explosion protected equipments and
distributions must not be operated in Zone
0 or 20 hazardous areas.
The requirements of EN 61241-0, -1 and
60079-0 regarding excessive dust deposits
and temperature must be considered by
the user.
The technical data indicated in point 3 as
well as those indicated in the technical
documentation
supplied
equipment, must be observed
It is necessary to ensure that the power
dissipation of equipment is not exceeded
(see technical documents supplied with the
equipment). The temperature class and
explosion group stated on the equipment
and distributions shall be observed. To
ensure adherence to the temperature class
stated on the type label of the equipment,
the permissible ambient temperature, the
rated terminal cross section and the self
heating of the equipment mainly due to
the power dissipation shall be taken into
account (test criterion for the self heating
is an overload of 10%).
Modifications or design changes to
equipment and distributions that affect
the explosion protection are not permitted.
They shall be used for their intended
purpose and shall be in a perfect and clean
state.
Only original COOPER Crouse-Hinds parts
may be used as replacements and for
repairs.
Repairs
that
affect
the
protection may only be carried out by
COOPER Crouse-Hinds or by a qualified
electrician in compliance with the respec-
tive national regulations.
Prior to being put into operation, the boxes
shall be checked in accordance with the
instructions as per section 6.
The operator is required to ensure that
the overall current of a distribution with
bus bar systems does not exceed the values
stated in the technical data of the
equipment.
Distributions mounted on a floor frame
shall be safeguarded against falling over.
Before initial operation, any foreign
matter shall be removed from the
equipment, do not keep this operation
instructions not technical documentation
inside the equipment during its operation.
The national safety rules and regulations
for the prevention of accidents, as well as
the safety instructions, like this text set in
bold-italics in these operating instructions
manual, shall be observed!
Cooper Crouse-Hinds, S.A.
5
Explosion protected switchgear equipments and racks Serie: GUB
2. Conformity with standards
This equipment is conform to the standards
specified in the EC-Declaration of conformity. It
has been designed, manufactured and tested
according to the state of the art and to
DIN EN ISO 9001, 94/9 EC: Equipment and
3. Technical data
Apparatus marking acc. to 94/9/EG directive:
II 2(1/2) G
II 2(1/2) D
Explosion protection symbol of other types of protection of built-in or used explosion protected components
are stated on the type label of the equipments.
EC-type examination certificate:
Rated voltage:
Ratet current:
Bus bar current:
Maximum permissible power dissipation inside
of enclosures:
with
the
For temperature class
GUB 00
GUB 20
GUB 30
Terminals capacity:
Perm. ambient temperature:
Special low temperature:
The actual permissible Ta range for each equipment is stated on the type label of the enclosures.
Perm. storage temperature in original packing:
Degree of protection EN/IEC 60529:
Insulation class acc. to EN/IEC 60598:
Enclosure material (standard version):
Enclosure surface finish:
Colour of enclosure (standard version):
Wall or standing framework:
Dimensions of equipments:
Cable entries:
- Dimensional drawings
- dimensions in mm
X = fixing dimensions
explosion
- approx. dimensions
protective systems intended for use in potentially
explosive atmospheres. The equipment fulfill
further requirements, such as the EC directive
on electromagnetic compatibility (2004/108/EC).
Ex d [ia Ga/ib Gb] IIC T4/T6 Gb
Ex t [ia Ga/ib Gb] IIIC T85ºC/T105ºC/T135ºC Db
LOM 04 ATEX2018
max. 750V
(some components up to 14KV, ask for)
max. 250A
max. 150A
Tamb. up to +40ºC
T4
T5
T6
max.
150W 85W
60W
max.
255W 145W 100W
max.
360W 200W 140W
max, 120mm
2
-20ºC up to +40ºC / +55ºC
-60ºC up to +40ºC / +55ºC
-40°C to +60ºC
IP 67
I
Aluminium alloy casting (Cu free)
Plastic powder coating
RAL 7032, cover RAL 7016
Iron U-profile painted or galvanized acc. to
application
See technical documentation supplied with
products
See technical documentation supplied with
products
Tamb. up to +55ºC
T4
T5
T6
125W
60W 35W
205W
100W 50W
300W
140W 70W

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gub 00Gub 20Gub 30

Tabla de contenido