Vega 900 Handbook
Environmental Specifications:
Description
Use
Temperature
Humidity
Altitude
Pressure
Orientation
Material Group
Pollution Degree
Overvoltage Category
Class
Weight
IP Rating
nd
* 3000m for 60601-1 2
** Option "I" can not be vertical with the inlet face accessible.
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth - 2.25 - 2.35kVDC
Primary mains circuits to transformer core - 4.25 - 4.35kVDC**
Primary mains circuits to secondary -4.25 - 4.35kVDC**
Outputs to each other and to earth are isolated to 200VDC.
**This test is not possible with Y capacitors fitted to the unit as damage to these capacitors may occur. It is also
necessary to short circuit the outputs together and to earth
Safety Approvals:
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
UL/CSA62368-1 UL Recognised. C-UL for Canada
IEC / EN60950-1 - CE mark.
IEC/EN60950-1, IEC/EN62368-1, IEC/EN 61010-1 and IEC/EN60601-1 - CB Report and Certificate.
CE marking when applied to any Vega 900 product indicates compliance with the Low Voltage Directive in that it
complies with EN60950-1 and with the ROHS Directive.
UL/CSA 61010-1: UL + C–UL approval
UL/CSA 60601-1: UL + C–UL approval
Fusing: Internal fuse (F1) 16A/250V fast acting HBC fuse 6.3x32mm
Symbols:
AC
EARTH
N
Fast-ons
0 to 50°C (derating 2.5%°C above 50°C to 65°C - Not
covered by approvals).
5 to 95% RH non-condensing
-200m to 5000m*
54kPa to 106kPa.
Horizontal with chassis lowest, on either side or vertical
with the airflow upwards.**
ed, IEC inlet and cooling options D and E.
N – Neutral
L
Operation
Indoor
IIIb
2
II
I
2 kg (Dependent on configuration)
IPX0
L – Live
N
Terminal block
Page 14 of 34
Storage
-40°C to +85°C
5% to 95% RH non-
condensing
-200m to 5000m.
54kPa to 106kPa
All
L
17155 issue 26, Sept 2019
-