INSTRUCTION MANUAL
SPECIFICATIONS
Model
Loudspeaker
Rated Power (RMS)
Power Taps 100 V
Impedance
Sensitivity
SPL
Sensitivity EN-54
Freq. Response
Cutout Size
Dispersion 1kHz / 4kHz
Operating temperature
Dimension (mm)
Weight
Finish
Colour
Power selection
EN54 standard
Other standards
INSTALLATION GUIDE
A-226CEN Version 1.1
Loudspeaker for voice alarm systems for fire detection and fire alarm systems for buildings
Impedance
100 V
10 W
1k
6 W
1k6
3 W
3k3
1.5 W
6k6 k
–
Common Common
1/1
At WARNING:
. Installation by qualified personnel only.
. Speakers must be wired in parallel and connected to
the correct line terminals of amplifier.
. Ensure that all speakers have the same polarity with
respect to each other.
Do not select another tapings if the speaker is in use.
.
No naked flame sources, such as lighted candles,
.
should be placed on the apparatus
A-226CEN
6,5"
10 W
10 W, 6 W, 3 W & 1,5 W
1 kΩ, 1k6 Ω, 3k3 Ω & 6k6 Ω
91,2 dB SPL at 1 W /1 m IEC268-5
101,2 dB SPL at 10 W /1 m IEC268-5
72,9 dB SPL at 1 W /4 m
65 ~ 24.000 Hz
Ø 194 mm
180º / 44º (-6 dB)
-20ºC ~ +80ºC
Ø 220 x 134 (depth)
2,02 kg
Steel, metallic grille
White (RAL9010)
Transformer taps
Ceiling Loudspeaker, 10W, Type A
CE-Symbol according 93/68EWG
VA special. In compliance with BS-5839, part 8.
70 V
5 W
3W
1,5 W
0,75 W
CEILING SPEAKER
EN 54-24:2008
Ref. No.: DOP_A226CEN
ID-Code: A226CEN
1438/CPR/0472
A-226CEN
.