2,3: Conformidad
•
IEC 687 (0,2% Exactitudes)
•
ANSI C12.20 (0,2% EXACTITUDES)
•
Resistencia De la Oleada C37.90.1 Del ANSI (IEEE)
•
ANSI C62.41 (Explosión)
•
IEC1000-4-2: ESD
•
IEC1000-4-3: Inmunidad Irradiada
•
IEC1000-4-4: Transitorio Rápido
•
IEC1000-4-5: Inmunidad De la Oleada
2,4: Exactitud
Measured Parameters
Voltage L-N
Voltage L-L
Current Phase
Current Neutral (Calculated)
+/- Watts
+/- VARs
+/- VARh
Frequency
% of Load Bar
* Accuracy Stated for 5 amp secondary WYE or Delta onnections. For 1 amp secondary or 2.5
element connections, add 0.1% of Full Scale + 1 digit to accuracy specification.
E Electro Industries/Gauge Tech
Meter Accuracy by Measured Parameters
Accuracy
Reading*
2.0% F.S.
+/- WH
VA
VAh
PF
+/- 0.01 Hz
%THD
2.0% F.S.
1-120%
% of
Display Range
0.1%
0-9999 V or kV Autoscale
0.1%
0-9999 V or kV Autoscale
0.1%
0-9999 A or kA Autoscale
0-9999 A or kA Autoscale
0.2%
0-9999 Watts, kWatts, MWatts
0.2%
5 to 8 Digits Programmable
0.2%
0-9999 VARs, kVARs, MVARs
0.2%
5 to 8 Digits Programmable
0.2%
0-9999 VA, kVA, MVA
0.2%
5 to 8 Digits Programmable
0.2%
+/- 0.5 to 1.0
45 to 65 Hz
0 to 100%
10 Segment Resolution Scalable
Doc. # ES145701
30