Included:
(5) 1 x 4 Terminal Blocks
(2) Screws
(1) Long Power Supply Jumper
(6) 3.9k Ohm
End of Line Resistors
Shipped on Board:
(2) Shunts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
compatible system control panel. Contact System Sensor for a list
of compatible detectors. The CZ-6 Module shall be mounted in a
suitably grounded Metallic Cabinet for EMC compliance.
WIRING
NOTE:
All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. All wiring to the CZ-6 is done via terminal blocks. In order
to properly make electrical connections strip approximately
5 mm of insulation from the end of wire, sliding the bare end
3.9K EOL
RESISTOR
(INCLUDED)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
+
FROM PANEL OR
–
PREVIOUS DEVICE
+
–
TO NEXT DEVICE
D500-67-00
(2) 3.2cm Stand offs
(3) Shunts
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY
+
+
–
–
CLASS B IDC (TYPICAL)
(+)
(–)
POWER-LIMITED
AND SUPERVISED
COMMUNICATION LINE 32 VDC MAX.
TWISTED PAIR IS RECOMMENDED.
Figure 1: Interface two-wire conventional detectors.
1. To use a common power supply between multiple CZ-6 modules, connect a long power supply
jumper from T5 or T6 to T5 or T6 on the adjacent CZ-6 module.
of the wire under the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module
(between 01 and 94).
The remaining modules are automatically assigned to the next
five higher addresses. For example, if the base address switch
is set to 28, the next five modules will be addressed to 29, 30,
31, 32 and 33.
DO NOT set the lowest address above 94, as the other modules
will be assigned to nonexistent addresses.
4. A shunt is provided to disable a maximum of two unused
modules. Modules are disabled from the highest address and
work downward. If two modules are disabled, the lowest four
addresses will be functional, while the highest two will be dis-
abled. For example, if the shunt for Address Disable is placed
on "two" and the base switch is set to 28, the modules will be
assigned to 28, 29, 30 and 31 while disabling the highest two
positions.
NOTE:
Place unused shunts on single pin to store on board for
future use.
WIRING NOTES
• All external power supplies must be power limited with battery
back-up.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.