Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2.5
Powering Down the Loads and UPS
Follow these steps to turn off the power of the UPS:
1. Turn off the power to loads connected to the UPS. Refer to the operating instructions for each load.
2. Turn the UPS switch to the "
" position.
2.6
Cleaning
! Before cleaning, turn off the switch of the UPS. Unplug the UPS from the power outlet.
! Also unplug the battery cable for the Long Back up Time model.
! Clean all surfaces with a soft, lint-free cloth that you have dampened in a mild solution of detergent and water. The
cloth must not be too wet.
WARNING-
1. Never spill water or cleaning fluid inside the unit. Should this happen accidentally, call immediately your
maintenance authority.
2.Do not use scouring pads, steel wool, harsh chemical agents, or anything that can damage the surface of
the unit
2.7
Storage
If you plan to store the UPS, there is a risk that the battery might discharge to the point where it is permanently
discharged. To prevent this from happening, follow these steps before storing the unit:
1. Fully charge the battery before storing the unit.
2. Recharge the battery for 24 hours at intervals not greater than 3 months.
2.8

Battery Maintenance

The battery should be serviced only by the qualified technicians.
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×4 (CSB GP1270-F2 CSB GP1272-F2,
OMEGA 1000
GS PE12V7.2) battery for replacement.
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×6 (CSB GP1270-F2,CSB GP1272-F2,
OMEGA 2000
GS PE12V72) battery for replacement
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×10 (CSB GP1270-F2,
OMEGA 3000
CSB GP1272-F2, GS PE12V72) battery for replacement.
3
Troubleshooting
This chapter describes problems you may encounter when using the UPS and the possible solution to these problems.
Also by the different LEDs display and buzzer beeping to let the user easily communicate with service people.
3.1
Indicators of LEDs and Buzzer
×:Off
":On
LEDs
×:Off
Buzzer BP: Continuous
----: Every 4 seconds
====: Every second
**-**: 2 times every second
?: Depends on the Alarm condition
LEDs Display
OVER
LINE
BYPASS
INV
ALARM
LOAD
"
×
"
×
×
"
"
"
×
×
×
×
×
×
"
×
×
"
×
×
×
×
"
×
×
×
×
×
"
"
×
"
×
"
N/A
×
×
"
"
N/A
-|-: Every 15 seconds
Buzzer
Main mode operating
×
Main mode operating
Transferring from
×
Bypass to Inverter
Battery mode
Check the ac utility or the
----
operating
fuse on the rear panel
Battery discharges
-|-
over 30 minutes
====
Battery low warning
Unplug the least critical
×
Full load condition
equipment
Unplug the least critical
**-**
Over load condition
equipment
Refer to 3.2 description and
BP
Fault
call the service people
21
3.2
Indicators of LED in Alarm Status
When the "Alarm" LED is on, please write down the LEDs bar display (from bottom to top) and contact to the service
people.
LED 1,2 On
LED 1,3 On
LED 1,4 On
LED 1,5 On
LED 1,2,4 On
LED 1,2,5 On
LED 1,3,5 On
LED 1,4,5 On
Specifications
Model
Rated Power
Operation
Input
Output
Battery
Audible
alarm
Environment
Dimension
N/A
Weight (Net)
N/A
N/A
N/A
N/A
Inverter over voltage
Inverter under voltage
Over temperature
Charging over voltage
Output short circuit
BUS over voltage
PFC or Charger malfunction
Over load occurred in battery mode operating
OMEGA 1000
1000VA/700W
Voltage
Current
6A max
Frequency
Power Factor
Phase
Voltage
Frequency
Waveform
Stable
Overload
Peak current
Transfer Time
Inverter Mode #$ Bypass Mode : <4mS
DC Voltage
48VDC
Quantity
12VDC/7AH×4pcs
Charging Current
Back-Up Time
10~15 Minutes (Depends on the Load Size)
Recharging Time
8~10 Hours (Recovery to 90% Capacity)
Battery Discharge
Discharge over 30 minutes
Battery Low
Overload
Fault
Acoustic Noise
<45dBA(1 meter)
Temperature
0-40°C
Relative Humidity
Altitude
(D)467mm×
(W)190mm×
(H)255mm
22Kgs
22
OMEGA 2000
OMEGA 3000
2000 VA / 1400 W
3000VA/2100W
True On-Line High Frequency UPS
160-270VAC
12A max
16A max
50(60)Hz+/-5%
>0.95 (Full load)
Single Phase / H+N+GND
220/230/240VAC+/-2%
50(60)Hz+/-0.5%
True Sinewave
110-140% for 20 seconds
>140% for 10 cycles
Line Mode #$ Battery Mode : 0mS
72 VDC
120VDC
12VDC/7AH×6pcs
12VDC/7AH×10pcs
1A
Sounding every 4 seconds
Sounding every 15 seconds
Sounding every second
Rush beeping
Continuously beeping
<50dBA(1 meter)
0-40°C
0-40°C
<95%(Non-condensing)
<3000 meter
(D)532mm×
(D)470mm×
(W)190mm×
(W)225mm×
(H)255mm
(H)480mm
29Kgs
49Kgs

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Omega 2000Omega 3000

Tabla de contenido