Stove rotating
The wall distances for rotating installation are present-
ed below.
80 cm
45°
Fig.5 Stove rotating, installed straight in corner
A = Position of combustion air line
routed up from the bottom
20 cm
45°
Fig.6 Stove rotating, installed diagonally in corner
A = Position of combustion air line
routed up from the bottom
80 cm
A
45°
45°
A
Assembly sequence
● If intended, install the OEC (see chapter "OEC
installation").
● The Ø 150 mm stovepipe needs to be connected at
the top of the appliance.
● Install the pipe lining (provided on site) in the chim-
ney. The connection height can be individually spec-
ified for a top stovepipe connection, however should
not exceed 1.5 m from the connector sleeve. No
combustible material is permitted within a radius of
20 cm around the stove pipe.
● Connect the stovepipe at both connection points
with stove putty so that the stove pipe is permanent-
ly sealed.
● Push the stove onto its planned position and orient it
so that the stovepipe fits into the pipe lining.
The stovepipe connections must be tight. The
stovepipe must not protrude into the chimney.
Bear in mind that on partition walls in accordance
with test specification EN 13240 the temperature
of 85°C can be reached, and with light wallpaper
or similar combustible construction materials this
can result in colour changes.
17