5. MALFUNCTIONS • WARNINGS
FAULT
1
Inserting the mains plug
1. No current in the mains socket or
• A and B are not illuminated
2. defective fuse in fullymains plug or
• Ventilator is o
3. defective energy saving lamp illuminant.
2
after the self-test
1. Possible defect of the device or
• C and D flash
2. Defect of the monitoring circuitry
• 5 beep sounds
• Ventilator is o
during operation
3
1. Foreign matter may possibly be in or on the (air flow)
• A and C are illuminated
• intervall sound (30 sec.)
2. Possible defect of the integrated extraction air
• Ventilator is o
4
during operation
The filter has almost reached its saturation limit; a timely (filter
• A is illuminated
monitoring) replacement is called for!
• D flashes
5
during operation
The filter is almost fully saturated and the ventilator has been
• A and D are illuminated
switched o . The filter must now be changed quickly.
• Alarm tone 2 sounds out every
hour
• Ventilator is o
6
during operation
The permissible operating time of the filter has expired. The
• A and D are illuminated
filter must now be changed quickly.
• Alarm tone 1 sounds out every
hour
ALARM SOUNDS
There are two di erent alarm sounds. If both are simultaneously activated, they ring out after one
another at an interval of approx. 6 seconds.
Tone sequence 1: short – short – long
Tone sequence 2: long – short – long – short
6. VENTILATION ADJUSTMENT • MONITORING
The ventilator capacity is su cient for a minimum ten-fold change of air for those cabinet models
listed under the „Purpose" item. The faultless ventilation function is automatically controlled by a
monitoring electronics system. A di erential pressure measurement device monitors air volu-
mes in the extraction air shaft. An alarm is triggered (C3) when the air rated value is undercut by
around 50 %. The optical alarm only stops when the rated value is again attained.
7. POTENTIAL FREE ALARM CONTACT
In order to use the potential-free alarm contact, the supplied three-pin plug must be used. Only the two outer
terminals are connected to the plug! The contact is designed for a maximum DC voltage of 30 V DC or an
AC voltage of 230 V AC. The maximum current load is 10 A. The switch contact is closed when de-
energized! As soon as mains voltage is applied and there is no malfunction (device "ready for operation"),
the switch is open.
REASON – ACTION
extraction air opening (to be removed) or
ventilator.
Internal
alarm contact
CAUTION:
The potential-free alarm contact must not be used to switch large loads. It is only intended for a mal-
function of the air circulation filter attachment by a signal light, horn or similar. to signal.
The connection must be carried out by a qualified electrician!
NOTES - must be observed!
The C13 cable must be removed before replacing the fuses
please contact your dealer or our costumer service:
+49 6051 92 20 0* (* at local rates in the german fixed network)
please contact your dealer or our costumer service:
+49 6051 92 20 0* (* at local rates in the german fixed network)
please contact your dealer or our costumer service:
+49 6051 92 20 0* (* at local rates in the german fixed network)
please contact your dealer or our costumer service:
+49 6051 92 20 0* (* at local rates in the german fixed network)
please contact your dealer or our costumer service:
+49 6051 92 20 0* (* at local rates in the german fixed network)
Connector
EN
(AC) / (DC)
(AC) / (DC)
11
11