Select the relay operating mode (direct "dI" or reverse "rE") with the
"up" ( ) or "down" ( ) key and confirm with "T"
POWER
ACTIVE
2
Set the set-point value for the measurement selected (visible on the display
display). Use the "up" ( ) or "down" ( ) keys to set the flashing digit
and "pK" to go to the next digit.
Press "T" to confirm
1
POWER
ACTIVE
2
3
Set the differential value (hysteresis) with the same procedure as that for
the set-point
Set the relay activation delay value (in seconds) with the same procedure
as that for the set-point
Note: if the energy operation is selected (active for relay 1 or reactive
for relay 2), the set-up movements from latching mode onwards will
not be displayed, as they serve no purpose
In this case, the relays will not operate as alarms, but as consumption
indicators for active/reactive energy
pK
W
ACTIVE
W
ACTIVE
T
- 60 -
User's Manual - ANRET Q-R / M-R