Product Information; Scope Of Delivery; Description And Function - salmson SC-Fire Electric Instalacion Y Puesta En Servicio

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5 Product information

5.1 Type key
Example:
S
S = Salmson
CTRL
Control
SC
Smart Control = control unit
F
F = fire fighting purposes
1x
Number of pumps
7.7 A
Maximum rated motor current [A]
T4
T = 3 phases; 4 = 400 V
DOL
Direct online (direct starting)
SD
Star delta (star-delta starting)
FM
Frame mounted (on a base frame)
BM
Base mounted (free-standing cabinet)
ND3
New Design switchbox 400 x 1300 x 250 mm
ND4
New Design switchbox 400 x 950 x 250 mm
E
Switchgear for electric pump
5.2
Technical data (standard version)
Mains supply voltage [V]:
Frequency [Hz]:
Control voltage [V]:
Max. current consumption [A]:
Protection class:
Max. fuse protection on mains side [A]:
Ambient temperature [°C]:
Electrical safety:
Alarm/signalling contact

5.3 Scope of delivery

• Switchgear
• Wiring diagram
• Installation and operating instructions
• Test report acc. to EN 60204-1
5.4 Accessories

6 Description and function

6.1 Description of the product (Fig. 1)
6.1.1 Function description
The switchgear is used to control an individual
electric pump in sprinkler systems, in accordance
with EN 12845. The pump can be switched on and
off by the control depending on the pressure. The
system's operating statuses, such as standby,
pump operation, fault etc., are displayed visually
by LEDs on the door and operating parameters
such as current or voltage values are shown on the
display. The system is operated using the rotary
knob and the buttons in the door.
Potential-free contacts are available for forward-
ing run or fault signals messages to the building
management system.
Installation and operating instructions Salmson SC-Fire Electric
3~400 V (L1, L2, L3, PE)
50/60 Hz
230 VAC; 24 VDC
See rating plate
IP 54
See wiring diagram
0 to +40°C
Degree of contamination II
250 VAC, 1 A
6.1.2 Set-up of the switchgear (Fig. 1)
The set-up of the switchgear depends on the
capacity of the pump to be connected. It consists
of the following main components:
• Main switch: Switches the switchgear on/off
(Fig. 1, item 2)
• Human-machine interface (HMI): signal lamps or
display for indicating the operating status (e.g.
standby, fault, and rated pump current), rotary
knob and buttons for menu selection, parameter
input and operation (Fig. 1, item 1)
• Base board: printed circuit board with microcon-
troller (Fig. 1, item 6)
• Measurement board: converting current and volt-
age values (Fig. 1, item 7)
• Transformer: 3-phase pump current measure-
ment (Fig. 1, item 4)
• Fuse protection for drives: fusing for the pump
motor by means of fusible cut-outs (Fig. 1, item 3)
• Contactors/contactor combinations: contactors
for switching on the pumps (Fig. 1, item 5)
English
31

Publicidad

Tabla de contenido
loading

Tabla de contenido