Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

LEVEL A

LEVL A
Function
Options
Linear Input Scaling
Please read in conjunction with Linear Input Set-up Procedure on page 6.
An.hi
-1999 to 9999
Adjusts required scale maximum
An.Lo
-1999 to 9999
Adjusts required scale minimum
hi.in
0.1 to 50.0
Configure input maximum
Lo.in
0.0 to 49.9
Configure Input minimum
This setting must be at least 0.1 less than the setting for hi.in above.
Note: Refer to Linear Input conversion factors detailed in the Set-up Procedure on page 6.
dECP
000.0 to 00.00
Scale resolution
NB. Once the Linear Input option has been selected, the setting here over -rides the scale
resolution setting di.SP in Level 2 and will affect the following display readings:
Level A:
An.hi ; An.Lo ; Set.3 ; hYS.3
Level 1:
bAnd ; ofSt ; SPrr ; SEt2 ; bnd.2
Level 2:
hiSC ; LoSC
Level 3:
SPAn ; ZEro ; rEAd ; tECh
SP3 SETTINGS
SP3.A [nonE]
dV.hi dV.lo bAnd FS.hi FS.Lo EoP
Main SP3 operating mode
SP3.b [nonE]
LtCh hoLd Lt.ho
Subsidiary SP3 operating mode
SEt.3
0 to 2500
SP3 setpoint adjustment
hyS.3
0.1 to 100% of hiSC
Set SP3 hysteresis
10
[Factory settings] shown in brackets
[1000]
[0]
[50.0]
[10.0]
[0000]
[0]
[20]
Will be affected by dECP settings in Level A
Function
Options
brn.3 [uPSC]
uPSC or dnSC
Sensor burn-out / break protection
Select upscale or downscale
rEV.3 [3d]
3d or 3r
Reverse SP3 output mode
Select direct or reverse operation
[Factory settings] shown in brackets

Publicidad

Tabla de contenido
loading

Productos relacionados para CAL Controls 9500P

Tabla de contenido