FUNCTION LIST (LEVEL P) PROGRAMMER
LEVEL P
LEVL P
Access Level P from Level 1. Press and hold
Function
Press
or
to change
Program number
ProG
Run Program
run
Power failure recovery mode
Fail
Program start value
St.V
Ramp rate time units
SPru
Segment number
SEG
16
Settings [Factory settings] shown in brackets
Press
or
to change
Add new programs (1 to 31)
[1]
Program not running
[oFF]
Run program
on
Pause program
hoLd
Delete program
Edit dEL
Insert new program
Edit inS
Copy another program
Edit CoPy
Paste copied program
Edit PStE
Reset to program start
[rSEt]
Continue from interruption
Cont
Hold at interruption (User re-start)
hoLd
Process value
[PV]
Setpoint value
SP
Ramp rate adjust in hours
[hour]
Ramp rate adjust in minutes
60 s
Add new segments (1 to 126)
[1]
See examples of EDIT procedures (page 18)
Deleting a Program automatically re-numbers those programs with higher numbers
Until memory full. See page 11 for further explanation and memory allocation table
on page 17.
Function
Sub-functions
Press
or
to change
Define segment type
TyPE
SPr
SoAK
StEP
LooP
CALL
Edit dEL
Edit inS
Settings [Factory settings] shown
in brackets
Press
or
to change
Ramp to next target setpoint
[100] Setpoint ramp rate Units per
SPrr
hour/minute (0-9990) (as set at
Spru above)
(Segment target setpoint)
t.SP
adjustable over instrument's
configured range
Hold back [oFF] sets the
hb.u
permitted band size for the
measured value to deviate from
the ramp setpoint before the
program is 'held back' waiting for
the measured value to catch up.
(0.1 to 150 units)
Hold setpoint for pre-set time [10]
Soak time, adjust in minutes
Sint
(cont.-1440) x 0.1
Step to new target setpoint (Set
tSP as above)
Re-cycle program
[1] Set number of program loops
PCYC
up to 999, or continuous loop
Call up another program by
number to import into this
program
(nonE) Number of Program called
Sub.P
at Call above
Delete segment
Insert new segment †