Storage, transport and disposal
Storage
Do not remove the control gear from its original
packaging until the time of installation.
Keep this manual with the control gear for future
use.
Do not store in direct sunlight or close to any
heat source.
Transport
Observe temperature and humidity specifications
during periods of transport.
(-25°C to +55°C without condensation).
Unpacking
After unpacking, check for physical damage that
may impact on the safety of the control gear such as
a damaged enclosure, dislodged cable glands etc.
Observe the local regulations and dispose of any
packaging material accordingly.
Disposal
Observe the local regulations and dispose of any
control gear accordingly. This product contains
electrical and electronic components and should be
disposed of accordingly.
Technical specifications and model
parameters
The tables below summarize the technical
attributes, specification and model parameters of the
SubStart3P
range. Models may differ with respect to
®
current overload characteristics and motor currents.
The connector terminals are suitable for copper (Cu)
wire.
Model Parameters
Motor
Rating
3~ 400V 50Hz
(kW)
0,37
SS037P3
0,55
SS055P3
0,75
SS075P3
1,10
SS110P3
1,50
SS150P3
2,20
SS220P3
3,0
SS300P3
3,7
SS370P3
4,0
SS400P3
5,5
SS550P3
7,5
SS750P3
2
Type
Model
2
Number
288 500 3510
288 501 3510
288 502 3510
288 503 3510
288 504 3510
288 505 3510
288 506 3510
288 507 3510
288 508 3510
288 509 3510
288 510 3510
Current Ratings
Motor
Rating (kW)
0,37
0,55
0,75
1,1
1,5
2,2
3,0
3,7
4,0
5,5
7,5
Specifications
Mechanical Specification
Protection level
Environment
Altitude
External dimen-
sions
Weight
Mounting
Storage tempera-
ture
Operation
temperature
Humidity
Electrical Specifications
1
Working Voltage
Rated insulation
voltage
Rated short-time
withstand current
Rated conditio-
nal short-circuit
current
Current
Power
Standards
IEC/EN 61439 - 1 : 2010
(400V/50Hz)
Nom.
Starting
3
Current
(A)
Current
1,1
1,6
2
2,8
3,9
5,5
7,5
9
9,9
12,6
17,1
IP 54
This equipment is suitable for
environment B according to
IEC/EN 61439-1 : 2010
max 2000m above sea level
190x184x106mm <= 4kW
250x256x140mm >= 5,5kW
1,2 kg <= 4kW
2,3 kg >= 5,5kW
Wall mounting (mounting
hardware provided)
-25°C to +55°C
- 5°C to +40°C
50% at 40°C (without con-
densation)
3~ / 50Hz
380 - 415V / -10% +6%
400 VAC
50 kA
50 kA
5A, 9A, 16 A
0,37kW - 7,5kW
4
(A)
5,4
7,4
10,6
16
20,7
29,8
42
52,3
57
77,2
99,3
GB