Cuenod NC4 R101 Instrucciones De Montaje página 25

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Installation
a (mm)
b (mm)
NC4/6
85-104 150-170
M8
NC9
95-104 150-170
M8
Altitude correction
Pump - suction (H +) or filling(H -)
Altitude (m)
H fictive (m)
0-500
501-800
801-1300
1301-1800
1801-2200
e.g.: altitude 1100m. Fictitious H = 1m
Real H 2 m.
H corrected for suction
2 + 1 = 3 m
H corrected for filling
2 - 1 = 1 m
Select in the table the Ø of the pipework depending on the
actual length between the tank and the pump.
If H corrected for induction exceeds 4m, allow for a transfer
pump. (max. pressure 2 bars).
c
d
45°
45°
H
Two-pipe pump
correct
60 l/h max
(m)
Ø 6/8mm Ø 8/10mm
4
17
3
14
2
12
1
10
0.5
9
0
8
-0.5
7
-1
6
-2
4
-3
-
0
0.5
1.0
1.5
2.0
04/2006 - Art. Nr. 13 010 551E
Assembly
Burner to boiler fixing is standardized.
If there is no hole drilled, the flange seal
can be used as a gauge.
• Position the flange and its seal on the
boiler.
The burner is assembled in position 1. If
necessary, it can be assembled in
position 2 or 3.
• Insert the burner's end piece into the
flange (penetration: see Boiler
Instructions).
• Tighten the collar while gently lifting
the burner
Fuel-oil connection
When linking the flexible hoses to
pipework, remember to allow for
removing the burner.
L (m)
Two-pipe connection
One-pipe
Use the diagram opposite to determine
US gal/h
the diameter and length of the pipework
0,60 1,00
according to the suction height (H+) or to
Ø 4/6mm
the filling height (H-)(for fuel-oil of 0.84
specific gravity, at a temperature of
54
80
48
10°C, in an installation with at the most
47
70
42
one valve, a nonreturn valve and four
40
60
36
34
51
30
elbows).
31
46
28
27
42
25
One-pipe connection
24
-
-
(for header tank only)
21
-
-
Undo the flexible return hose, remove
14
-
-
8
-
-
the connector and the branch plug.
Blank off with a cylindrical plug and a
seal.
Electrical connection
The electrical installation and the
burner's connection must be carried out
in accordance with the standards in
force.
The burner is delivered with a 7-pole
male plug into which are connected the
230V-50Hz single-phase power supply
with ground and the thermostat. (Figure
opposite).
Note: connection of an alarm between
S3 and N and of an hour counter
between B4 and N.
- Protection: 6.3A min
- Section of conductors: 1,5mm
2
.
25

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Nc6 r101Nc4 h101Nc6 h101Nc9 h101

Tabla de contenido