Refrigerant Pipe Connection - AUX AMW-NFH Serie Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Refrigerant pipe connection

Before installing, make sure that the height difference, the length of refrigerant pipe and number of bends
between indoor and outdoor units, meet the following specifications.
Max. lenght:
UNIT
Note: If the outdoor unit is installed above the indoor units and the sum
of all the tanks is more than 7m, an oil trap must be installed in the
gas pipe every 3 meters.
Additional charge
UNIT
AM2 (2x1)
Charged until
15m
Additional
charge
20 x (Total length - 15)
R32 (g)
AM2
AM3
AM4 / AM5
(2x1)
(3x1)
(4x1 / 5x1)
40
60
80
25
30
35
*(1)
*(1)
15
15
15
15
15
15
10
10
10
AM3 (3x1)
22,5m
20 x (Total length - 22,5)
46
Max. height difference:
Outdoor unit
*(1)
AM4 (4x1)
30m
20 x (Total length - 30)
Indoor unit
Indoor unit
10m
5m
10m
Indoor unit
AM5 (5x1)
37,5m
20 x (Total length- 37,5)

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

R32

Tabla de contenido