1. Safety instructions

For skilled electricians and instructed personnel in
accordance with national legislation, including the
relevant standards and, where applicable, in acc.
with IEC 60079-17 on electrical apparatus for ex-
plosive atmospheres.
The floodlights must not be operated
in Zone 0 or 20!
The light fitting must not be use while exist
excessive layer of dust (> 5 mm, accd.
IEC 60079-10-2) !
The technical data indicated on the floodlights
are to be observed!
Changes of the design and modifications to the
floodlights are not permitted!
The floodlights shall be operated as intended
and only in undamaged and perfect condition!
Only genuine Cooper Crouse-Hinds
Cooper Crouse-Hinds spare
Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cooper Crouse-Hinds
parts may be used for replacement!
Repairs parts that affect the explosion protection
mode, may only be carried out by
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A. or a qualified
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
"electrician" and will subsequenctly have to be
cheked by an "expert"!
Do not keep these operating instructions
inside the floodlights during operation!
The national safety rules and regulations for
prevention of accidents and the following
safety instructions which are marked with an
(
) in these operating instruction, will have to
be observed!
2. Conformity with standards
This explosion protected floodlights meets the
requeriments of EN60079-1, EN60079-7,EN61241-1,
and EN60598.It also complies with
the EC Directives for "Apparatus and protective
systems for use inexplosive atmospheres"
(94/9/EC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in explosive
atmospheres, Zone 1 and 2 acc. to IEC60079-10-1 as
well as Zone 21 and 22 acc. to IEC 60079-10-2.

3. Technical data

Aplication:
II2GD
Class I
Ex de IIB T
Class II
Ex tD A21 IP66 T
Certificates:
BVS 09 ATEX E050X
IECEx-BKI 07.0041
Others on request
:
Serie of types
See Table 1
Lamps to be use:
See Table 1
Approval of the production
Quality assurance:
LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 66 / 67+
Insulation class
acc. EN60598:
I
o
Temperature of use:
-20
C to + 40
>40
o
C to + 55
Rated voltage:
See Table 1
Material of enclosure:
Metal aloy copper
free aluminium
painted polyester grey.
Material of glas
Borosilicate
Storage temperature in original
Packing
-50
o
C to + 60
Terminals capacity:
See wiring diagram
Entries of cables
Indirect entry:
2 x M25 x 1,5 ISO965-1,
one plugged
Dimensions:
See figure 3.
3)
Notes:
See table 2, thermal class and surface
temperature acc. the lamp used.
7
Cooper Crouse-Hinds, S.A.
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have
to be observed!
¡Transport and storage of the floodlights
is permitted in original packaging only!
¡Pay attention when mounting or repairing
the luminaire, dont damage the fire-finish
of the glass adquired during moulding
(abrasions, sanding, etc.) that can
weaking their mechanical functions.
repairing the floodlights, dont damage
the fire-finish of the glass adquired
during moulding (abrasions,
sanding, etc.) that can weaking their
mechanical functions!
¡Montage position!
Opening and closing the floodlights
¡The opening of luminaire always shall be
without voltage!.
¡The luminaire is well closed when the gap
of the flange joints, in every side of the
enclosure are < 0,15mm. Torque of bolts
thinckness > 30 Nm.
There're Exd joints in the frame - lamp
housing, and in the cover - controlgear
housing!
Dimensions for mounting: See figures 3
Accesories for mounting:
See Cooper Crouse-Hinds
Cooper Crouse-Hinds catalogue
Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cable entries
Mounting the selected cable entries
(cableglands) acc. type and dimensions of
the main conection cable, following their
manufacturer instructions.
The cable entries devices has to be a
protection mode ExeII
Unused cabe entries have to be closed by
a correspondante certifyed blanking plug.
If the original blanking plugs are used ,
3)
these must be tightened with 15 Nm
3)
torque.
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps
for the supplied luminaire. See indications
in the general label of the luminaire and in
this instructions!
o
C
o
C
5. Taking into operation
¡Prior to operation check the floodlights
for its proper funtioning and installation
in compliance with these operting
instructions and others applicable
regulations!.
Only carry out insulation measurements between
o
C
PE and external conductor L1 (L1, L2, L3) as well as
between PE and N.
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
6.
Servicing
When servicing, in particular those components that
affect the explosion protection , will have to
cheked, e.g.:
Inspection
I.e. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
See wiring diagram.
Repairing
For repair electrical equipments in protection mode
is suggested follow the instructions indicated
in IEC 60079-19.
Subject to alteration or supplement of this product
without any advertisement before.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive
atmospheres, e.g. IEC 60079-17as well as
the general rules of engineering!
¡For dust explosive appication, pay
special attention d'ont have present clust
layers abore 5mm on side of the
apparatus!
The responsable of the safe use of these
apparatus is the property.
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas for their firm fit.
Lamp replacement in acc. with the
manufacturer instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have
to be greassed permanentlly in order to
ensure it protection in front of the
corrosion, water ingrees and seize-up
problems. Cleaning rest of greasse and
corrosion no using sharp metallic devices
who can damage the surface of the joint,
and greasing they using apropiate
greasse therminally and chemically stable
with a drop point > 200ºC like e.g.:
    
Molikote
BR2 plus.
¡When the housing need to be repeinted,
pay attention that the flameproof joints
rest without any part with coating.
Less for the PTFE coating, that in this
case ask Cooper Crouse-Hinds, S.A. for
the correct process!
¡The nationals regulations have to be
observed!
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires
have to be disconnected from the main
conection!.
¡The nationals regulations have to be
observed.The tasks of repairing have to be
made by "qualified" personnel!.
¡The reparation of the sealed part between
the collarand the glass have to be done
by Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.. The users
Cooper Crouse-Hinds, S.A.
are not authorized to repair this sealed
part.
All reparations have to be done without
voltage!.
¡Only use genuine
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A.
Cooper Crouse-Hinds, S.A. spare parts!.