Attention :
Please ensure that the test electrodes
(probe tips) make good contact with two
phases of a three-phase mains while test-
ing the phase rotation. For absolute deter-
mination of a clock-wise phase rotation it is
necessary to make a negative phase rota-
tion test after changing the phases. The
indication "" or "" can be affected by
unfavorable light conditions, by protective
clothing or in insulated locations.
Firmly grasp the insulated grip of the
Tester probe L2, it is better for the
sensitivity of the phase rotation test.

8. RCD Voltage Test

Voltage Test with RCD Trip Test
During voltage tests in systems equipped
with RCD circuit breakers, a RCD switch
can be tripped at a nominal residual current
of 10mA or 30mA by measuring the voltage
between L and PE.
These Testers EV
/ EV
are equipped
with an internal load enabling the tripping
of an RCD protection device of 10mA or
30mA.