Parameters menu

Press the programming button "M" (detail 2 - fig. 1) for 5 seconds to access the parameters menu. The
parameter "u01" is displayed: identified by the message SET 01. Press the button "P" (detail 5 - fig. 1)
to scroll the list of parameters.
Just press the + and - buttons (details 4 and 6 - fig. 1) to modify the value of a parameter: the modification
will be automatically stored. After modifying the parameter, it is necessary to wait 3 seconds: the data
flashes and is stored.
Table 1
Parameters
u01
Delivery setpoint adjustment
u02
Burner max. power
u03
Burner operation methods (see par. 3.1)
Press the "operation mode selection - M" button (detail 2 – fig.1) for 5 seconds to exit the menu.
Service parameters Menu
Press the programming button "P" (detail 5 - fig. 1) for 10 seconds to access the parameters menu. The
parameter "t01" is displayed: identified by the message SET 01. Press the button "P" (detail 5 - fig. 1)
to scroll the list of parameters.
To modify the value of a parameter just press the + and - buttons (details 4 and 6 – fig. 1): the change
will be automatically stored. After modifying the parameter, it is necessary to wait 3 seconds: the data
flashes and is stored.
Table 2
Parameters
t01
t02
t03
t04
t05
t06
t07
t08
t09
t10
t11
t12
t13
t14
t15
t16
t17
t18
t19
Press the programming button "P" (detail 5 - fig. 1) for 10 seconds to exit the menu.
40
Description
Description
Pellet loading function
Delivery probe
Fan setpoint in Lighting
Auger activation time in Lighting
Adjustment calculation timer(Only with Modulating burner
operation with delivery Probe)
Ramp function timer
Period (activation+deactivation time) with auger operating
(from Power 1 to Power 5)
Fan setpoint at Power 1
Auger activation time at Power 1
Fan setpoint at Power 2
Auger activation time at Power 2
Fan setpoint at Power 3
Auger activation time at Power 3
Fan setpoint at Power 4
Auger activation time at Power 4
Fan setpoint at Power 5
Auger activation time at Power 5
Burner operation selection (Only with Delivery Probe)
Post-Ventilation time 2
Cod. 3540I810 - 03/2009 (Rev. 00)
Range
30 - 80 °C
80 °C
1 - 5
5
0 - 2
0
Range
0=Disabled, 1=Enabled
0=Disabled
0=Disabled, 1=Enabled
1=Enabled
0-200 Pa
51 Pa
0-100 (1=4 seconds)
12
0-100 seconds
5 seconds
0-100 seconds
80 seconds
0-50 seconds
10 seconds
0-200 Pa
38 Pa
0-100 (100=10 seconds)
28
0-200 Pa
74 Pa
0-100 (100=10 seconds)
38
0-200 Pa
133 Pa
0-100 (100=10 seconds)
46
0-200 Pa
150 Pa
0-100 (100=10 seconds)
53
0-200 Pa
170 Pa
0-100 (100=10 seconds)
56
0=On/Off, 1=Modulating
0=On/Off
0-100 (100=10 seconds)
99
SUN P7