Solving of root cause failures:
1.
After over-heating, the PCB itself needs time to cool down. At lower temperatures < 85°C the
controller can be restarted.
2.
For security reasons, any short interruption of the sensor signal will lead to a stand-by of the
controller.
5
Set-up menu
5.1
Adjustment of set-Point
 
Set-Point Temperature entered to be achieved by the heating system. Value can be entered between
upper and lower limits set by operator.
Set-Point Temperature can be adjusted by entering into the Set-Up Menu by simultaneous pressing
Enter Button
and Back Button
for several seconds.  
Pressing Up
or Down
buttons to change value inside the tolerance-band set by user.
Confirmation of chosen set point temperature by pressing Enter But-
Back Button
. By not confirmation the Set-Point stays unchanged.
6

Settings menu

Enter set-up menu by simultaneous pressing Enter Button
entered and adjusted inside the menu.
Pressing Up
or Down
Buttons to navigate through the menu.
Choose any specific point inside the menu by pushing the Enter Button
Exit or quit any specific point or entry inside the menu by pushing the Back Button
®
© BriskHeat
Corporation
BH-510 Operation Manual
ton
or Cancel entry by
and Back Button
. All settings can be
.
.
®
. All rights reserved.
7
6.1

Structure of menu:

6.2
Set-point
See 5.1
6.3
Lower / upper limits for set-point temperature
Limits for minimum and maximum temperature concerning the variation of the set-point temperature. The
values of lower and upper limits can be set between 0°C and 999°C.
6.4
Band of tolerance
Current actual temperatures inside the set tolerance-band are considered balanced to the set-point
value, signaled by the green LED-light on and the symbol
tings between ±0,5°C and ±10°C.
A wider band of tolerance chosen will lead to fewer switches of the Hybrid-Relay and accordingly to a
better life-time. For more accurate controlled temperature values the tolerance-band has to be reduced
up to the needs of the application.
6.5
Type of sensor
6.5.1
Auto detection
The auto detection recognises the afterward following sensors:
PT100 (2-, 3- or 4-wires)
PT1000 (2-, 3- or 4-wires)
Thermocouple (Type K)
The Auto detection can be started by pressing enter
The found sensor type has to be confirmed by pressing enter
Back
can stop the process of detection and parameters stay unchanged.
All other types of sensors have to be chosen manually.
®
© BriskHeat
Corporation
BH-510 Operation Manual
inside the display appearing. Range set-
inside the sensor menu.
again.
®
. All rights reserved.
8