6.5.2
Manual selection of sensor
List of all sensors (including auto detectible) will show up in menu. Please, select matching sensor type
out of list and confirm by pressing enter
.
6.6
Unit
Selection between degree Celsius and degree Fahrenheit is available
6.7
Language
Languages available: Japanese, English and German
(note: English wording accompanies all languages in this point of menu)
6.8
System info
Information about the product: firmware and hardware version
7
Controller On / Off
The controller switches automatically on with the power supply connected.
On/ Off of controller: simultaneous pressing Up Button
8
Terminal connections
•
Line unfused: Clamp for phase; power supply for currents >10 A or >2300 W at 230 VAC / 1100
W at 110 VAC. Protection against overload and over-currents has to be secured by
external fuse!
•
Line 10 A Fuse int.: Clamp for phase; power supply for currents <10 A or <2300 W at 230 VAC /
1100 W at 110 VAC. Fix mounted fuse inside controller.
•
N: Clamp for neutral conductor of power supply
•
N Heat: Clamp for neutral conductor of heater
•
L Heat: Clamp for phase of heater
K2: Thermocouples (Polarity!)
K3: Resistance temperature sensors. (Pt100/1000, Nickel120, NTC10k/100k, etc.)
®
© BriskHeat
Corporation
BH-510 Operation Manual
and Down Button
for several seconds
®
. All rights reserved.
9
2-wire sensor, clamps K3.1 and K3.4
3-wire sensor, clamps K3.1, K3.2 and K3.4
4-wire sensor, clamps K3.1, K3.2, K3.3 and K3.4
K4: Potential-free signal for external monitoring or control systems
Earth Connection: Screw thread for earth connection of controller and heater (cable lug supplied)
®
© BriskHeat
Corporation
BH-510 Operation Manual
®
. All rights reserved.