FUNCTIONS
1. RESIDUAL CURRENT CIRCUIT BREAKER: this is a vital security device of the power distributor!
When someone accidentally touches one of the mains conductors, a current leak through the body of
this person could result in a lethal (deadly) shock. As soon as such current leakage in the installation is
detected, the power distributor outputs will be disconnected. The maximum allowable current leakage is
set to 30mA. Under normal working conditions the lever on the right should be in upward position.
Important: the functions of this device should be tested every 30days by pushing the test button on top:
as a result the outputs should be immediately disconnected from the mains.
2. INDIVIDUAL 32A CIRCUIT BREAKERS: each of the 2 outputs (A, B) is secured by C32 (32A - 3P+N)
automatic circuit breakers. Under normal working conditions the lever should point to the right.
3. INDIVIDUAL 16A CIRCUIT BREAKERS: each of the 3 phases is secured by C16 (16A - 1P+N)
automatic circuit breakers. Under normal working conditions the lever should be in upward position.
4. VOLT METERS: each of the 3 phases have their individual 3-digit voltage meter.
5. AMPERE METERS: each of the 3 phases have their individual 3-digit ampere meter.
6. 63A INPUT: 1,5m long mains input cable (3x 63A, 5wire), equipped with CEE (3P+N+E) inlet plug.
7. 32A OUTPUT "A": CEE (3P+N+E) outlet socket (3x 32A, 5wire), can be used to feed-through up to 32A
3phase current. Make sure that the total input current will not be exceeded!
8. 32A OUTPUT "B": CEE (3P+N+E) outlet socket (3x 32A, 5wire), can be used to feed-through up to 32A
3phase current. Make sure that the total input current will not be exceeded!
9. 16A OUTPUT PHASE1: a 230V/16A output socket, connected to phase1 (L1)
10. 16A OUTPUT PHASE2: a 230V/16A output socket, connected to phase2 (L2)
11. 16A OUTPUT PHASE3: a 230V/16A output socket, connected to phase3 (L3)
12. GROUND CONNECTION OF THE HOUSING