be possible for air to be drawn in for combustion pur-
poses, and the air heated by the built-in fireplace (the
convection air) must be able to flow freely within the
space to be heated; see following figure.
A
B
A
C
A
Convection air current
B
Radiated heat
C
Air supply from the room to be heated
When building the hearth, follow these instruc-
tions for the convection space:
The top of the convection space must be closed air-
tight using a cover plate of non-flammable and
heat-resistant material.
The cover plate must be level and placed at least
600 mm below the flue opening in the ceiling.
Air inlet grates must be fitted at the bottom of the
Subject to change because of technical improvements
hearth to allow for ambient air intake. The minimum
air inlet opening is 500 cm
ficiently ventilated, you must provide for outside air
to be allowed in by means of the outside air con-
nection kit or an optional adjustable damper.
Air outlet grates must be installed at the top of the
hearth just below the cover plate. The minimum air
outlet opening is 600 cm
Follow the instruction below when building the
hearth:
1. Build the base of the hearth and fit the air inlet
2. Build the hearth up to the smoke dome.
3. The inside of the convection space may, if
09-20021-129
4. Build the rest of the hearth up to the flue opening
5. Close the convection space with the cover plate.
6. Put the air outlet grates under the cover plate.
7. Make an opening above the cover plate in order to
2
. If the space is not suf-
2
.
The inlet and outlet grates are available as
options.
Do not use combustible material in the con-
vection space, and avoid the effect of thermal
bridging when using materials that conduct
heat.
grates into the masonry.
You can place the air inlet grates on all sides of
the base.
Make sure the door of the appliance can swing
freely over the hearth floor.
Ensure that a clearance of 2 mm is maintained
between the built-in fireplace and the masonry
to accommodate the thermal expansion of the
fireplace.
desired, be cladded with reflective, insulating
material.
Additional cladding of the convection space pre-
vents unnecessary thermal radiation towards
outer walls and/or adjacent rooms. It also pre-
vents damage to the hearth wall insulation.
hole in the ceiling.
The masonry should not rest on the fireplace.
Use a support such as a steel beam. Leave a
clearance of at least 3 mm between the sup-
port and the appliance.
prevent any pressure build-up.