Ducting Requirements - Samsung DVE45T6005 Serie Manual De Usuario

Ocultar thumbs Ver también para DVE45T6005 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ducting requirements

Weather hood type
No. of 90° elbows
0
1
2
3
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer's vent system with an existing exhaust system:
• Make sure the exhaust system meets all applicable local, state, and national regulations.
• Verify you are not using flexible plastic duct.
• Make sure to check for and remove all lint buildup from inside the existing ducts.
• Confirm the duct is not kinked or crushed.
• Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column
or be less than 0. Note that these values are measured with the dryer running with a
manometer presented to the exhaust duct that connects to the dryer. The dryer tumbler
must be empty and lint filter clean.
Untitled-4 15
Recommended
4" (10.2 cm)
Rigid
80 ft. (24.4 m)
68 ft. (20.7 m)
57 ft. (17.4 m)
47 ft. (14.3 m)
Use only for short-run
installation
2.5" (6.4 cm)
Rigid
74 ft. (22.6 m)
62 ft. (18.9 m)
51 ft. (15.5 m)
41 ft. (12.5 m)
English 15
2020-01-14
12:11:40

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Dveg45t6005 serieDve45t6000 serieDveg45t6000 serie

Tabla de contenido