AUX
RED(+)
NOTE:
If one or more of the AUX/BELL/LS outputs is overloaded and the SMPS shuts
down, the SMPS must be reset, using the ProSYS software as follows:
From the ProSYS main user menu press
option), or enter and exit the installation-programming mode (refer to the
ProSYS Installation Guide).
If overload still exists, perform manual reset as follows:
Disconnect all loads from the AUX/COM terminals for at least 10 seconds before
you reconnect any load to the AUX/COM terminals. Then perform Overload
Restore again, using ProSYS main user menu (see Installer Programming Menu
on page 13).
Used to connect the GND terminal to the main box ground pin
GROUND
(see illustration on page 6). Use 16 AWG (at least).
(Earth)
Used for connection of the AC terminals (see illustration on
AC
page 6) to the transformer outputs (16.5VAC/50 VA).
NOTE:
A readily accessible disconnect device shall be incorporated in the building
installation wiring.
Relay Output Wiring
NOTE:
If the SMPS Utility Output is to be used, take into consideration that in such a
case one available ProSYS output expander is utilized!
The SMPS Utility Output module comprises two relays (Dry Contacts) that are
of the "Change Over" type.
Terminal block description:
NO = Normally Open
NC = Normally Closed
C = Common
Connect each of the SMPS relay outputs according to your preferred
configuration.
Used together with the COM (-) terminal to apply power to
Aux. devices (e.g. PIRs, smoke/glass break detectors and
any other devices that require 12VDC power supply). Total
current consumption from the SMPS (Via The Aux./COM and
BELL/LS terminals) is 3A.
[2] [0] [2] (Overload Restore
9