Installation
Option : Hydrobox powered via outdoor unit
<1 phase>
Power
supply
~/N
230 V
50 Hz
* If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
*2 Affix label A that is included with the manuals near each wiring diagram for hydrobox and outdoor units.
<3 phase>
Power
supply
3N~
400 V
50 Hz
* If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power line.
*2 Affix label A that is included with the manuals near each wiring diagram for hydrobox and outdoor units.
Hydrobox - Outdoor unit
Hydrobox - Outdoor unit earth
Hydrobox - Outdoor unit S - S2
Hydrobox - Outdoor unit S2 - S3
*. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
*3. The values given in the table above are not always measured against the ground value.
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. The lack of the power supply capacity might cause chattering.
9
Wiring
Earth
circuit
leakage
breaker or
circuit
Isolating
breaker
switch
*
Power
supply
~/N
230 V
50 Hz
<Figure 4.5.5>
Electrical connections  phase
Description
Power supply
Booster heater (Primary circuit)
~/N 230 V 50 Hz
Earth
Wiring
leakage
circuit
circuit
breaker or
breaker
Isolating
*
switch
Power supply
3~ 400 V 50 Hz (EH**-YM9(E)B)
3~ 230 V 50 Hz (EHSC-TM9B)
Electrical connections 3 phase
Description
Booster heater (Primary circuit)
*2
3 × .5 (polar)
*2
 × Min. .5
*3
230 V AC
*3
24 V DC
Outdoor unit
L
S1
N
S2
S3
Wiring
circuit
breaker or
Isolating
switch
Capacity
Breaker
2 kW
6 A *
6 kW
32 A *
Outdoor unit
L1
S1
L2
S2
L3
S3
N
Wiring
circuit
breaker or
Isolating
switch
<Figure 4.5.6>
Power supply
Capacity
Breaker
3~ 400 V 50 Hz
9 kW
3~ 230 V 50 Hz
9 kW
Hydrobox
TB1
L
N
To control
board
S1
S2
S3
ECB1
For
L
booster
heater
N
(Primary circuit)
Wiring
2.5 mm²
6.0 mm²
Hydrobox
TB1
L1
L2
To control
board
S1
S2
S3
ECB1
For
L1
booster
heater
L2
(Primary circuit)
L3
Wiring
6 A *
2.5 mm²
32 A *
6.0 mm²