10. TROUBLESHOOTING LIST MERTIK GV60
No
ACTION
1.
Option: wall switch START:
press ON button > wall switch
works.
1.
Manual transmitter START:
press both buttons to start
ignition sequence.
Beep will occur each second
OK
2.
Magnet unit in gas valve is
energised (audible click)
OK
Possible problem/cause
NO
Bent pin on switch, or cable
not operating properly.
NO
Manual transmitter battery
low.
Receiver batteries low.
Optional mains adapter not
operating properly.
Check coding of transmitter
and receiver.
Transmitter/receiver range
limited.
Optional wall switch / cabling
not operating properly.
Receiver fuse blown (in older
versions only).
NO
No beep
Impulse magnet not
operating properly.
NO
3 short
Receiver batteries low.
beeps
NO
1 long beep
ON/OFF switch on gas valve
in OFF position
8-wire cable between receiver
and gas valve defective /
poor contact.
Switch cable disconnected.
Motor not operating properly. Replace gas valve.
Micro switch on gas valve not
operating properly.
Solution
Straighten pin, replace wall
switch or cable.
Replace battery, 2x AAA 1.5V
quality alkaline!
Replace batteries, 2x AA 1.5V
quality alkaline!
Check mains adapter.
Learn in new code, see
instructions and label on
receiver.
1.
Move antenna cable,
see instructions.
2.
Replace receiver.
Replace wall switch / cabling.
Replace receiver.
Replace gas valve.
Replace batteries, 4x 1.5V AA
quality alkaline!
Set switch to ON.
Check cable, especially in case
of plug connection.
Check switch cable, see fig. 1
on page 18
Replace gas valve.
Page.15