Use As Boiler Pump - BRÖTJE HEP 25-180-10 Manual De Montaje

Ocultar thumbs Ver también para HEP 25-180-10:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 58
Commissioning
GB

4.3 Use as boiler pump

Function
Configuration
DHW actuator Q3
PWM output P1
Function
Heating circuit 1
Pump speed min
Pump speed max
Heating circuit 2
Pump speed min
Pump speed max
Heating circuit 3
Pump speed min
Pump speed max
Boiler
Pump speed min
Pump speed max
DHW cylinder
Pump speed min
Pump speed max
26
Boiler pump with DHW heating via 3-way diverter valve
If the pump HEP is used as a boiler pump for DHW heating via a 3-way valve, apply
the settings given in the following table.
Prog. no.
5731
6085
Set the minimum and maximum pump speeds in accordance with the system con-
figuration under menu items Heating circuit 1-heating circuit 3, Boiler and DHW
storage tank
Prog. no.
882
883
1182
1183
1482
1483
2322
2323
5101
5102
Variable speed pump HEP 25-180-10
Setting level
Setting
E
Diverter valve
E
Boiler pump Q1
Setting level
Set value
E
E
E
E
E
E
E
E
E
E
7303554-03 08.12

Publicidad

Tabla de contenido
loading

Tabla de contenido