Overloads On The Ups - Riello Dialog Plus Serie Manual De Usuario

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Table 2
Battery level
0%~20%
20%~40%
40%~60%
60%~80%
80%~100%
Table 3
Input Voltage
190V~200V
200V~230V
230V~250V
250V~260V
>260V
Tab. 4
Load level
0~5%
5~25%
25%~50%
50%~75%
75%~102%
>102%
LED on with steady light
LED with flashing light on (1 flash per second)
O
VERLOADS ON THE
The following table shows how the UPS reacts when mains and battery overloads occur and indicates the time
that the UPS will remain powered.
OVERLOAD LEVEL
102% < Load ≤ 109%
110% <= Load ≤ 130%
130% < Load ≤ 150%
Load > 150%
Short circuit
1
2
1
2
25
50
UPS
LOAD POWER TIMES
(off mains)
Switches to bypass after 30 min
Switches to bypass after 30 sec
Switches to bypass after 10 sec
Switches to bypass after 0.5 sec
Immediate shutdown
I
NSTALLATION AND
Battery LED bar
3
4
Battery LED bar
3
4
Load LED bar
75
100
LOAD POWER TIME
(off battery)
Shutdown after 30 min (if battery
back up time allows)
Shutdown after 30 sec
Shutdown after 10 sec
Shutdown after 0.5 sec
Immediate shutdown
U
SE
5
5
!
49