Electrical installation
Wiring the CAN bus
Bus cable length
)
Note!
It is absolutely necessary to comply with the permissible cable lengths.
ƒ
Please note the reduction of the total cable length due to the signal delay
ƒ
of the repeater (^ 42).
Mixed operation
ƒ
– Mixed operation refers to different nodes which are connected to the
same network.
– If the total cable lengths of the nodes are different at the same baud
rate, the smaller value must be used to determine the max. cable
length.
1. Please check the compliance with the total cable length in Tab. 1.
The total cable length is determined by the baud rate.
Baud rate [kbit/s]
10
20
50
125
250
500
800
1000
Tab. 1
Total cable length
40
Max. bus length [m]
8000
3900
1500
630
290
110
40
17