Installing 2 Exterior Hoods - Broan HRV90H Serie Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. INSTALLATION
(CONT'D)
3.9 I
2 E
NSTALLING
XTERIOR
Choose an appropriate location to install the exterior hoods:
There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination
There must be a minimum distance of 18 inches (457 mm) from the ground
Make sure the intake hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards)
from sources of contamination such as:
• High efficiency furnace vent
• Any exhaust from a combustion source
• Gas meter exhaust, gas barbecue-grill
• Garbage bin
Refer to figure below for connecting insulated ducts to the exterior hoods. An "Anti-gust intake hood" should be installed in regions where
a lot of snow is expected to fall.
E
XHAUST HOOD
VD0028
H
OODS
I
NTAKE HOOD
18"
(457
)
MM
6'
(1.8
)
M
!
WARNING
6" Ø
(152
)
MM
18"
(457
)
MM
O
PTIONAL
DUCT LOCATION
T
APE AND DUCT TIE
- 16 -
6'
(1.8
)
M
18" (457
)
MM

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Erv90hc serieHrv90htHrv90hsErv90hctErv90hcs

Tabla de contenido