Mode 3: Ouput Setpoint When S1 Low
When the S1 input is at an electrically low state or wired to the unit's common, the DP4
will force its output to a percentage which corresponds to the programmed jog setpoint,
parameter 31. Once the S1 input returns to an electrically high (+5V) state or allowed to
fl oat disconnected, the output will once again correspond to the display value.
Mode 4: Output Setpoint When S1 High
When the S1 input is at an electrically high (+5V) state or allowed to fl oat disconnected,
the DP4 will force its output to a percentage which corresponds to the programmed jog
setpoint, parameter 31. Once the S1 input returns to an electrically low state or wired to
the unit's common, the output will once again correspond to the display value.
Mode 5: Output 100% When S1 Low
When the S1 input is at an electrically low state or wired to the unit's common, the DP4 will
force its output to 100%. Once the S1 input returns to an electrically high (+5V) state or
allowed to fl oat disconnected, the output will once again correspond to the display value.
Mode 6: Output 100% When S1 High
When the S1 input is at an electrically high (+5V) state or allowed to fl oat disconnected, the
DP4 will force its output to 100%. Once the S1 input returns to an electrically low state or
wired to the unit's common, the output will once again correspond to the display value.
Parameter 31 – Signal Input 1 (S1) Setpoint
When the S1 confi guration, parameter 30, is set to one of the setpoint (jog) modes(modes 3
or 4), this parameter defi nes the jog setpoint in display units. This parameter is always set in
display units.
Parameter 35 – Signal Input 2 (S2) Confi guration
This parameter determines the operating mode of signal input 2 (S2).
Mode 1: Output 0% When S2 Low
When the S2 input is at an electrically low state or wired to the unit's common, the DP4
will force its output to 0%. Once the S2 input returns to an electrically high (+5V) state or
allowed to fl oat disconnected, the output will once again correspond to the display value.
Mode 2: Output 0% When S2 High
When the S2 input is at an electrically high (+5V) state or allowed to fl oat disconnected,
the DP4 will force its output to 0%. Once the S2 input returns to an electrically low state
or wired to the unit's common, the output will once again correspond to the display value.
Mode 3: Ouput Setpoint When S2 Low
When the S2 input is at an electrically low state or wired to the unit's common, the DP4
will force its output to a percentage which corresponds to the programmed jog setpoint,
parameter 36. Once the S2 input returns to an electrically high (+5V) state or allowed to
fl oat disconnected, the output will once again correspond to the display value.
Mode 4: Output Setpoint When S2 High
When the S2 input is at an electrically high (+5V) state or allowed to fl oat disconnected,
the DP4 will force its output to a percentage which corresponds to the programmed jog
setpoint, parameter 36. Once the S2 input returns to an electrically low state or wired to
the unit's common, the output will once again correspond to the display value.
Mode 5: Output 100% When S2 Low
When the S2 input is at an electrically low state or wired to the unit's common, the DP4 will
force its output to 100%. Once the S2 input returns to an electrically high (+5V) state or
allowed to fl oat disconnected, the output will once again correspond to the display value.
Mode 6: Output 100% When S2 High
When the S2 input is at an electrically high (+5V) state or allowed to fl oat disconnected, the
DP4 will force its output to 100%. Once the S2 input returns to an electrically low state or
wired to the unit's common, the output will once again correspond to the display value.
Parameter 36 – Signal Input 2 (S2) Setpoint
When the S2 confi guration, parameter 35, is set to one of the setpoint (jog) modes(modes 3
or 4), this parameter defi nes the jog setpoint in display units. This parameter is always set in
display units.