Stop Input
This menu permits to select the functions associated to the
command of STOP .
no
The input STOP is not available.
ProS
The input STOP stops the door: pressing the command START
the door continues the motion.
invE
The command STOP stops the door: at the next START the
door starts moving in the opposite direction.
NOTE: during the pause, the STOP command will stop the pause time
count, the next START command will always close the door.
Photocell input
This menu allows enabling the input for photocells (see paragraph
"Installation").
no
input disabled (ignored by the control unit).
No jumper with the common is required.
CF.CH input enabled even at standstill door too: the opening
movement does not start if photocell is interrupted.
CH
input enabled for the closing phase only
Warning: if you select this option, you must disable photocell
test.
Test of safety devices
In order to achieve a safer operation for the user, the unit performs a
safety devices operational test, before a normal working cycle.
If no operational faults are found, the door starts moving. Otherwise, it
will stand still and the flashing light will stay onfor 5 sec. The whole
test cycle lasts less than one second.
no
function not active
Foto
test enabled only for photocells
CoSt
test enabled only for safety edges
Ft.Co
test enabled either for photocells or for safety edges
WARNING: The PHOTOCELL OPERATIONAL TEST should be working
in order to grant more safety during installation and programming.
WARNING: it is possible to test safety edges only if a control
unit specially provided for this function has been installed.
If using conductive rubbers do not activate the test, as the control unit
continuously check their functionality.
30