3.4
Supply Air Sensor Wiring
Install the supply air sensor in the supply air plenum at least
2-3 feet after the heat exchanger and coil. Make sure there
are no zone dampers before the supply air sensor.
Connect the supply air sensor to the zone panel as shown.
3.5
Transformer Wiring
Install the transformer using the instructions provided
by the manufacturer. Size the transformer to the damper
requirements. The zone panel has a built-in, self-resetting
fuse. The maximum damper power per panel is 35 VA at
24 VAC.
Connect the transformer to the zone panel as shown.
Note: Additional dampers or dampers with a higher current draw will require the use of a separate
slave relay.
3.6
Conventional System Wiring
Note: For a heat pump system, see Section 3.7.
Connect a conventional heating
system to the zone panel as shown.
For a single stage heating and cooling
system, the 2nd stage connections are
not used.
For a system using a dual transformer,
open jumper J1 (see Configuration
section, Figure 4). Make sure the the
neutrals (common) are connected.
SA1
SA2
RH
RC
1st stage
compressor
Y1
control
Y2
1st stage
G
control
G2
1st stage
W1
heat
AUX
control
W2
O/B
C
6
HOT
C
C
Dedicated
Zoning Transformer
24 VAC
2nd stage
compressor
control
fan
2nd stage
fan
control
2nd stage
heat
control
Plenum
24V
24C
Zone
Panel
HOT
C

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

140303

Tabla de contenido