Conettix Plug-in Communicator
Interface
4.5.2
Conexión a un panel de control SDI
1
D9412GV3
Commercial Protected-Premises Control Panel
Refer to the D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069)
for System Wiring Diagram, Issue A and for compatible smoke detectors. 2-wire Compatible Identifier "A".
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007:
UL Listed and Classified control unit Model D9412GV3, D7412GV3, or D7212GV3;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
PERIPHERAL DEVICE CONNECTIONS
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
Accessory Devices. For System Loading, refer to the D9412GV3/D7412GV3 Operation
and Installation Guide (P/N: F01U143070).
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
(P/N: F01U143070) for Power Requirements relating to Terminals 6 and 7 .
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12 V Lead Acid
NFPA
Batteries.
Style 4.0
Signaling
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code) and
Line
NFPA 72 (National Fire Alarm Code).
Circuits
Not suitable for remote station protected premises services where separate transmission circuits
are required for fire, supervisory (when applicable) and trouble signals when using D185.
D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary,
Proprietary, and Household Fire Alarm, and Central Station, Local, Proprietary,
Police Station Connect, Household Burglar Alarm and Encrypted Line Security when
communicating via a network.
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiating circuits the control panel has been approved for are A, M, W, SS.
The types of signaling the control panel has been approved for are DAC, OT, NC, RevPol.
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Short
0.0 - 1.3 VDC
Normal
2.0 - 3.0 VDC
Point 1 Point 2
Point 3 Point 4
Point 5 Point 6
Point 7 Point 8
Normal Operation
Open =AB-12 UL
Bell Box 220 kΩ
Operation Monitor LED
11
12
13
14
15
16
17
18
19
20
21
22
GREEN
Figura 4.6: Uso de un regletero de terminales o de cables de interconexión en un panel de control SDI (se muestra el panel de
control de la serie GV3)
Número: descripción
1: panel de control SDI compatible (se muestra el panel de control de la serie GV3)
2: B450
3: cables del regletero de terminales
4: Cable de interconexión
Bosch Security Systems, Inc.
WARNING!
To prevent risk of
electric shock,
2
disconnect AC
power and
telephone lines
before servicing.
SDI Connector
Reset Pin
Disable all except Battery
Charging and Programming
RED
POWER +
R
Y
YELLOW
DATA BUS A
G
DATA BUS B
GREEN
B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
3
26
ZONEX OUT 2
25
25
ZONEX IN 2
24
ZONEX POWER +
ZONEX COMMON
23
Point 8, S3 Option
Closed = 1 kΩ EOL
Pulses when Normal
Flickers when Ringing
Guía de instalación y funcionamiento
D9412GV3
Commercial Protected-Premises Control Panel
Refer to the D9412GV3/D7412GV3 Approved Applications Compliance Guide (P/N: F01U143069)
for System Wiring Diagram, Issue A and for compatible smoke detectors. 2-wire Compatible Identifier "A".
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007:
UL Listed and Classified control unit Model D9412GV3, D7412GV3, or D7212GV3;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RW;
UL Listed Local Bell
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
R
Accessory Devices. For System Loading, refer to the D9412GV3/D7412GV3 Operation
and Installation Guide (P/N: F01U143070).
All external connections except Terminal 5 (battery positive) are inherently power
Y
limited. Requirements for battery standby time might reduce allowable output.
G
(P/N: F01U143070) for Power Requirements relating to Terminals 6 and 7 .
B
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code) and
NFPA 72 (National Fire Alarm Code).
Not suitable for remote station protected premises services where separate transmission circuits
are required for fire, supervisory (when applicable) and trouble signals when using D185.
D9412GV3 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary,
Proprietary, and Household Fire Alarm, and Central Station, Local, Proprietary,
Police Station Connect, Household Burglar Alarm and Encrypted Line Security when
communicating via a network.
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiating circuits the control panel has been approved for are A, M, W, SS.
The types of signaling the control panel has been approved for are DAC, OT, NC, RevPol.
Point 1 Point 2
Point 3 Point 4
11
12
13
14
15
1
WARNING!
To prevent risk of
electric shock,
disconnect AC
power and
telephone lines
before servicing.
SDI Connector
Reset Pin
Disable all except Battery
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
Battery: Replace every 3 to
BLACK
COMMON
5 years with one or two Model
D126 or D1218 12 V Lead Acid
Batteries.
NFPA
ZONEX OUT 1
Style 4.0
Signaling
Line
ZONEX IN 1
Circuits
26
ZONEX OUT 2
25
ZONEX IN 2
25
ZONEX POWER +
24
VOLTAGE RANGES
Open
3.7 - 5.0 VDC
Short
0.0 - 1.3 VDC
ZONEX COMMON
23
Normal
2.0 - 3.0 VDC
Point 5 Point 6
Point 7 Point 8
Point 8, S3 Option
Closed = 1 kΩ EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 kΩ
Operation Monitor LED
Pulses when Normal
Flickers when Ringing
16
17
18
19
20
21
22
GREEN
2014.10 | 05 | F.01U.300.741
Instalación | es
17
2
R