Function List; Level 1 - CARLO GAVAZZI T2000 Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

FUNCTION LIST (LEVELS 1 TO 4)
Note: A Functions Menu is shown on page 3.

LEVEL 1

LEVL 1
Function
Options
SELECT AUTOTUNE
(see pages 4/5)
tunE [oFF]
on ParK At.Sp
Used to switch the Autotune feature on and off, to select ParK or Autotune at setpoint.
ParK temporarily turns the output(s) off. To use select ParK and exit program mode. To
disable re-enter program at tunE and select oFF.
SP1 OPERATING PARAMETERS
bAnD
0.1 to * C/°F
SP1 proportional band/Gain or Hysteresis
* 25% sensor maximum Proportional control eliminates the cycling of on-off control. Heater
power is reduced, by time proportioning action, across the proportional band.
int.t oFF
0.1 to 60 minutes
SP1 integral time/reset
Auto-corrects proportional control offset error
dEr.t oFF
1 - 200 seconds
SP1 derivate time/rate
Suppresses overshoot and speeds response to disturbances
dAC 0.5 - 5.0 x bAnd
SP1 derivative approach control dAC
Tunes warm-up characteristics, independent of normal operating conditions, by controlling
when derivative action starts during warm-up (smaller dAC value = nearer setpoint).
CyC.t A – –
on.oF
0.1 - 81 sec
SP1 proportional cycle-time (see pages 9/10)
Determines the cycle rate of the output device for proportional control. Select on.oF for
ON/OFF mode.
oFSt [0] to *
°C/°F
SP1 offset/manual reset
* ±50% bAnd. Applicable in proportional and ON/OFF mode with integral disable:
Int.t : oFF.
SP.LK [oFF]
on
Lock main setpoint
Locks the setpoint preventing unauthorised adjustment.
[Factory settings] shown in brackets
[10ºC/18ºF]
[5.0]
[25]
[1.5]
[20]
PROGRAMMER SETTINGS
(see page 5)
Function
Options
SPrr
[0] to 9995 deg/hour
Sets the ramp rate
SPrn on [oFF] hoLd
Switches the ramp on or off, or hold at last ramp value
SoAK – – [oFF]
0 to 1440 min
Sets the soak time
SP2 OPERATING PARAMETERS
(see page 6)
SEt.2
0 to * °C/°F
Adjust SP2 setpoint
* Deviation Alarms DV.hi, DV.Lo, bAnd 25% sensor maximum.
* Full scale alarms FS.hi, FS.Lo sensor range f/s
bnd.2
0.1 - * °C/°F
Adjust SP2 hysteresis or proportional band/gain
(see CyC.2 setting)
* 25% sensor f/s
CyC.2 [on.oFF]
0.1–81 seconds
Select SP2 ON/OFF or proportional cycle-time
Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for proportional
mode.
LEVEL 2
LEVL 2
MANUAL CONTROL MODES
SPI.P
0 to 100 % 'read only'
Read SP1 output percentage power
hAnd [oFF]
1 to 100 % (not in ON/OFF)
SP1 manual percentage power control
For manual control should a sensor fail. Record typical SP1.P values beforehand.
PL.1
100 to 0 % duty cycle [100]
Set SP1 power limit percentage
Limits maximum SP1 heating power during warm-up and in proportional band.
PL.2
100 to 0 % duty cycle [100]
Set SP2 percentage power limit (cooling)
[Factory settings] shown in brackets
[0]
[2.0 °C/3.6°F]
7

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido