Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

FPM-1000-ENC
Hinging and Unhinging the Door
The control panel comes from the factory with the door attached. For easy wiring, you can
unhinge the door (refer to Figure 3, Page 4).
Dead Front Door
The dead front door covers the electronics and batteries. It can be opened and removed
easily. The dead front door is attached at the bottom and secured at the top by fasteners
(refer to Figure 4, Page 4). The fasteners close by pushing the fastener head inward with finger
pressure (refer to Figure 4, Page 4, Item A) and open with a quarter-turn of the fastener head
(refer to Figure 4, Page 4, Item B).
Ground Wire Connections
When the mainboard is installed, connect the supplied ground wire between the door and the
enclosure using the supplied nuts (refer to Figure 5, Page 5, item 1). A second ground wire is
provided for connecting the ground to the dead front door (refer to Figure 5, Page 5, item 2).
Both grounds connect to the stud in the enclosure to the left of the mainboard.

Technical Data

Mechanics
Mounting holes
Cable entries
Material
Color
Dimensions (W x H x D)
Dimensions with trim ring (W x D)
Semi-flush mounted (H recessed / H flush)
Weight
-
-
-
Environmental Conditions
Environment
Operating temperature
Storage temperature
Relative humidity
Protection class as per IEC 60529
Bosch Security Systems, Inc.
Enclosure
Gross weight (including packaging and
manuals)
Complete panel (with one
FPE-1000-SLC and FPE-1000-CITY each,
without batteries)
3, on back
Triple knockouts (1/2, 3/4 and 1 in)
Cold rolled steel, 19 gauge (1.2 mm)
Red
14.5 in. x 4.3 in. x 22.7 in.
(36.8 cm x 10.9 cm x 57.7 cm)
17.5 in. x 25.6 in.(44.5 cm x 65.0 cm)
3.25 in. / 1.05 in. (8.25 cm / 2.7 cm)
18.1 lb (8.2 kg)
24.5 lb (11.1 kg)
25.8 lb (11.7 kg)
Indoor, dry
32 °F to 120 °F (0 °C to 49 °C)
14 °F to 131 °F (-10 °C to 55 °C)
Up to 95 %, non-condensing
IP 30
F.01U.133.409 | 2.0 | 2011.08
en
7

Publicidad

Tabla de contenido
loading

Tabla de contenido