INSTALLATION MANUAL
ECM5000 - ECM5000M - ECS5000 - ECS5000M - ECS8000 - ECS8000M
Surface mount or Mortice Electromagnetic locks
Installation with DPM300 - DPM500
(Door position monitoring)
DPM300
Fixed on the
electromagnetic lock
DPM300
Fixed on the armature
Roll pin
Armature plate
8] FAULT FINDING
PROBLEM
Door locking
The lock is not receiving DC current.
impossible
The lock and the armature are not
lined up with each other.
Holding
force
reduced
Low voltage or armature jammed.
Faulty reed
Voltage too low. Misalignment.
switch
8
position.eu.com
POSSIBLE CAUSE
SOLUTION
- Check that the wires are connected to the appropriate terminals.
- Check that the power supply is compatible.
- Check that the lock is connected to the circuit correctly.
- Check that the lock is connected to the circuit correctly.
- Check that the electromagnet and the armature
are properly aligned.
- Check that the contact faces are free from dirt and rust.
- Check that the armature is soft mounted.
- Check that the lock is receiving the correct power supply
satisfactorily.
- check the tightening of the armature and the condition
of the rubber.
- Check the power supply.
- Cable cross section to be determined according to the power
supply and the locking.
- e.g.: 2 x 1.5mm2 ≥ 10m.