Restrain Cable
Wrap conductors using 30 ft. (9 m) of 3/8 in. (9.5 mm) sisal rope or equivalent.
1) Begin wrapping conductors (A) 2.5 in. (64 mm) above circuit breaker. Wrap conductors five times, leaving 12 plus "X" ft. (4 + "X"m) of excess rope at the first and (B).
Pull rope (C) taut.
2) Wrap rope (D) several times until space between first two sets of conductors is completely filled. Weave final rope loop underneath previous loop (E).
Bring rope (F) through right-hand space. Pull rope taut.
3) Wrap rope (G) several times until space between second and third set of conductors is completely filled. Weave final rope loop (H) underneath previous loop as shown.
Pull rope taut.
4) Wrap rope four times around conductors 4 in. (102 mm) below where conductors exit enclosure (I). Pull rope (J) taut.
5) Wrap rope (K) several times until space between first two sets of conductors is completely filled. Bring rope (L) through right-hand space. Pull rope taut.
6) Wrap rope (M) several times until space between second and third set of conductors is completely filled.
Weave final rope loop (N) underneath previous loopas shown. Pull rope taut.
7) Tie rope End 1 and End 2 together as shown. Rope must be taut. Cut off excess rope and tape ends to prevent fraying.
8) In the same way, Wrap the lower conductors.
Installation Instructions
"X"
2.5 in.
[64 mm]
4 in.
[102 mm]
End 1
End 2
<Fig. 10> Wrap Rope
- 6 -
End 1
End 2