Gemini GEM-P400 Manul De Operacion página 77

Tabla de contenido

Publicidad

Water Connections continued-
Utility Models (See Figure 3)
All utility models are supplied with inlet and outlet nipples located in a plastic bag
attached to the water heater. The hot and cold water locations are identified on
the side of the water heater. Apply appropriate amount of thread sealant to the
provided nipples and install nipples into the side of the tank. For 20 gallon utility
models, install the supplied anode/nipple combination at the HOT outlet location.
Connect the hot and cold water lines to the nipples using unions. Install a listed
temperature-pressure relief valve in the opening on the side of the water heater.
Install a vacuum relief anti-siphon device in the cold water inlet line when using
side cold water connection.
The 6 and 12 gallon models are equipped for installation with either side or top
water connections. They are shipped from the factory with the alternate top
connections plugged. The alternate top inlet is supplied with a dip tube. If the top
water connections are needed, remove pipe plugs from the alternate top
connections, apply appropriate amount of thread sealant to the provided nipples
and install nipples in desired top location. Apply appropriate amount of thread
sealant to the pipe plugs and install pipe plugs in the side locations. Install a
vacuum relief anti-siphon device in the cold water inlet line when using side cold
water connection.
Figure 3
13

Publicidad

Tabla de contenido
loading

Tabla de contenido