Pressure Transducer Fail Shutdown
In the event that the pressure transducer signal should be lost, the system will shut the pump(s) off. During the
transducer fail error, the display will flash "SENSOR FAILURE" on the main display and the fault indicator will illuminate.
If the transducer failure is corrected, the display will return to its normal condition and normal pressure control will
resume.
Parameter Setup List
SETTING DESCRIPTION
Set Pressure
Start Diff Pressure
Lag Start Diff Pressure
Lag Stop Diff Pressure
Lag Stop Delay Time
Alternation Time
Pump 1 OL Amps
Pump 1 Voltage
Pump 2 OL Amps
Pump 2 Voltage
Sleep Frequency
Sleep Time
Xducer Max Range
Min Frequency
Max Frequency
PID Proportional Term
PID Integral Term
1st Accel Time
1st Decel Time
Accel 2 Switchover Freq
Accel/Decel Time
High Pressure Alarm
Run Dry Pressure
Run Dry Delay Time
Run Dry Restart Time
Set Pressure
Set Pressure is the target pressure to be maintained at the pump discharge. It cannot exceed the maximum range of the
pressure transducer.
Start Diff Pressure
The Start Diff. Pressure is the amount of pressure drop from the Set Pressure, at which the lead VFD will wake from
sleep and run to maintain the system pressure. The lead pump will start if the pressure drops below the Set Pressure
less the Start Diff. Pressure. Example: If the Set Pressure is 40 PSI and the Start Diff. Pressure is 5 PSI, the lead pump
will start when the pressure drops below 35 PSI.
Lag Start Diff Pressure
The Lag Start Diff. Pressure is the amount of pressure drop from Set Pressure, while the lead VFD is running full speed
and five seconds has passed, before the lag VFD is started. The lag VFD is run at full speed while in operation. The lead
VFD will not be allowed to enter sleep mode while the lag VFD is running.
Lag Stop Diff Pressure
The Lag Stop Diff. Pressure is the amount of pressure over the Set Pressure, after the Lag Stop Time has passed,
before the lag VFD is stopped.
VARIOspeed
3R Duplex User Manual
®
RANGE
0 to "Xducer Max Range" -0.1
0 to "Set Pressure" -1
0 to "Set Pressure" -1
0 to "Xducer Max Rng" - "Set Pressure"
0 to 999 seconds
1 to 168 hours
0 to VFD Amp Rating
0 to 1000 Volts
0 to VFD Amp Rating
0 to 1000 Volts
0 to "Max Frequency"
0 to 3600 seconds
0 to 1000 PSI
0 to "Max Frequency"
"Min Frequency" to 120 Hz
0.1 to 1000%
0.1 to 3600 seconds
0 to 3600 seconds
0 to 3600 seconds
0 to "Max Frequency"
0 to 3600 seconds
0 to "Xducer Max Range" - 0.1
0 to "Set Pressure" -1
0 to 6.0 minutes
0 to 999.9 minutes
DEFAULT
60.0 PSI
5 PSI
7.0 PSI
5.0 PSI
2.0 seconds
24 hours
Model Specific
Model Specific (240/480)
Model Specific
Model Specific (240/480)
35.0 Hz
10 seconds
200 PSI
30.0 Hz
60.0 HZ
100.0%
1.0 seconds
2 seconds
2 seconds
30 Hz
3 seconds
90.0 PSI
15 PSI
0.5 minutes
0.0 minutes (manual restart)
7