OPERATION
Register
Address
1052
1051
1053
1052
1054
1053
1055
1054
1056
1055
1057
1056
1058
1057
1059
1058
1060
1059
1061
1060
1062
1061
1063
1062
1064
1063
1065
1064
1066
1065
1067
1066
1068
1067
1069
1068
1070
1069
1071
1070
1072
1071
1073
1072
1074
1073
1075
1074
1076
1075
1077
1076
1078
1077
1079
1078
1080
1079
1081
1080
1082
1081
1083
1082
1084
1083
1085
1084
1086
1085
1087
1086
1088
1087
1089
1088
15
PMML0419A rev.1 - 05/2016
Description
Status Unit Mode
Status Circuit 1 Run/Stop
Status Heat. OTC Circuit 1
Status Cool. OTC Circuit 1 (*2)
Control Circuit 1: Water heating Fix Setting Temp
Control Circuit 1: Water cooling Fix Setting Temp (*2)
Status Circuit 1: Eco mode
Status Circuit 1: Heat ECO Offset Temperature
Status Circuit 1: Cool ECO Offset Temperature (*2)
Status Circuit 1: Thermostat Setting Temperature
Status Circuit 1: Thermostat Room Temperature
Status Circuit 1: Wireless Setting Temperature (*5)
Status Circuit 1: Wireless Room Temperature (*5)
Status Circuit 2 Run/Stop
Status Heat. OTC Circuit 2
Status Cool. OTC Circuit 2 (*2)
Status Circuit 2: Water heating Fix Setting Temp
Status Circuit 2: Water cooling Fix Setting Temp (*2)
Status Circuit 2: Eco mode
Status Circuit 2: Heat ECO Offset Temperature
Status Circuit 2: Cool ECO Offset Temperature (*2)
Status Circuit 2: Thermostat Setting Temperature
Status Circuit 2: Thermostat Room Temperature
Status Circuit 2: Wireless Setting Temperature (*5)
Status Circuit 2: Wireless Room Temperature (*5)
Status DHWT Run/Stop
Status DHWT Setting Temperature
Control DHW Boost
Status DHW Demand Mode
Status DHW Temperature
Status Swimming Pool Run/Stop
Status Swimming Pool Setting Temperature
Status Swimming Pool Temperature
Status Anti Legionella Run
Status Anti Legionella Setting Temperature
Status Block menu (*6)
Status BMS Alarm
Central Mode
Range
0: Cool (*2)
1: Heat
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
0~80 ºC(*3)
0~80 ºC(*3)
0: ECO
1: Comfort
1~10
1~10
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
0~80 ºC(*3)
0~80 ºC(*3)
0: ECO
1: Comfort
1~10
1~10
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
0: Stop
1: Run
0~80 ºC(*3)
0: Disable
1: Enable
0: Standard
1: High demand
-80~100 ºC (*1)
0: Stop
1: Run
0~80 ºC(*3)
-80~100 ºC (*1)
0: Stop
1: Run
0~80 ºC(*3)
0: No
1: Block
0: No
1: Alarm
0: Local
1: Air
2:Water
3: Full
Type
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R