POWERVAR
- SECURITY ONE UNINTERRUPTIBLE POWER MANAGER
? A battery (even a depleted one) can deliver very high currents when short-circuited.
There is a danger of electrical shock. Remove all watches, rings, bracelets or other
metal objects. Use only tools with insulated handles.
? Do not dispose of batteries in a fire. There is a danger of explosion. Do not dispose of
batteries in an environmentally unfriendly manner. Batteries may be returned to
POWERVAR for proper disposal.
? Do not open or mutilate the batteries. This may release electrolyte that
is toxic to the environment and harmful to the skin and eyes.
? Replacement batteries may be ordered from POWERVAR by phone or
via our website at www.powervar.com. If purchasing batteries from another source, be
sure to use the type and quantity of batteries described in the table in Section 10.
8.0 – USER REPLACEABLE BATTERY
Please note: Changing the batteries in this UPM is designed to be a safe and simple procedure. Batteries
may be replaced while the UPM is on and providing power to the connected load. You should remember,
however, that if a power outage occurs after the old batteries are disconnected and before the new batteries
are installed, power will be lost to your connected system and components.
Please note: If you have read and understood the cautions preceding this section, you may proceed with
the following steps. Consult Figure 6 to assist you in the following battery replacement procedure.
Battery Replacement
1.
Remove the two small screws from the bottom of the front panel that secure the front panel to the frame
of the UPM.
2.
Place thumbs at both corner edges of the top of the front panel. Push front panel down lightly to
disconnect.
3.
Carefully pull front panel away from unit taking care not to disengage any wires of the LED cable. Set
front panel on top of the unit.
4.
Disconnect the black battery Molex connector from the PC board.
5.
Remove the screws from the battery front stop plate.
6.
Carefully remove the battery front stop plate by tilting the plate sideways.
7.
Hold unit firmly and slowly remove the battery pack by pulling on the battery tab.
8.
Detach Molex connector assembly from old battery.
9.
Obtain a new battery pack.
18