6) INSTALLATION
Origo™ Arc are a three-phase welding rectifier, to be connected across three input phases. The mains
cable is connected to the circuit breaker. The primary terminal is reconnectable for different input voltages
(220, 380 or 440 V - 60Hz). The electrical diagram shows the different voltage connections procedures.
Remove the cover on the left panel and reconnect the terminal block as shown on the electric diagram.
Recommended cable areas and fuses ratings are listed below.
Connected the rectifier across three input phases and ground connection according to regulations.
TABLE 6.1
Voltage
(V)
220
380
440
IMPORTANT!: The grounding terminal is connected to the rectifier chassis. It
must to be connected to an efficient grounding point to the general power
supply system.
18
Origo™ Arc 256/406/456
Primary current (A)
Cable
for 60% duty cycle
(Cu - mm2)
256
406
456
87
91
109
63,5
48
49
54
44
45
220V 60Hz
01
02
380V 60Hz
01
02
440V 60Hz
01
02
Fuse delay (A) or
Circuit-breaker (A)
256
406
16,0
100
120
10,0
70
63
10,0
63
50
456
100
63
50