Spacer holder
ƒ
It is recommended that shut-off valves are fitted before and after the
energy meter to simplify removing the meter.
ƒ
The calculator should be installed in a conveniently accessible position
for service and operating personnel.
ƒ
Initial operation is to be carried out and recorded after installation.
3.

Installation of the temperature sensors

Handle the temperature sensor carefully!
Red: sensor in the hot line
Blue: sensor in the cold line
ƒ
Sensors must be installed symmetrically.
ƒ
The maximum cable length for PT100 and PT500 is 10 m.
ƒ
The connecting cables must not be shortened or extended.
ƒ
For DN 15 and DN 20, the sensors must be installed directly immersed.
ƒ
The free temperature sensor can be installed in a ball valve or in a
conformity- tested pocket for this type of sensor.
ƒ
Ensure that the temperature sensors are permanently connected dur-
ing operation.
ƒ
If the sensor is installed in a pocket, it must be inserted as far as the
bottom of the pocket and then secured.
ƒ
For installation in a ball valve, a 4-piece coupling set is enclosed in a
separate bag (see Fig. I).
Insert one O-ring in the sensor hole using the mounting pin supplied.
Français
Español
Wall mounting
-23-