Tifell Ecomax 50 SCW Instrucciones De Instalación, Uso Y Mantenimiento página 67

Caldera de condensación a gas de premezcla para calefacción
Tabla de contenido

Publicidad

CÓDIGO
FALLO
E15
SONDA DE RETORNO
E16
ELECTRIC FAN
E18
INSUFFICIENT
CIRCULATION
E21
GENERAL INTERNAL
BOARD ERROR
E22
PARAMETERS
PROGRAMMING REQUEST
E35
RESIDUAL FLAME
E40
SUPPLY VOLTAGE
2. MANTENIMIENTO
CAUSA POSIBLE
SOLUCIÓN
SONDA ESTROPEADA O
SUSTITUIRLA;
MAL CALIBRADA (VALOR DE
RESISTENCIA 10 KOHM A 25
°C NTC);
CONECTOR DE LA SONDA
COMPROBAR EL CABLEADO.
DESCONECTADO O HÚMEDO
ELECTRIC FAN BOARD
REPLACE IT;
BROKEN;
ELECTRIC FAN BROKEN;
REPLACE IT;
FAULTY POWER SUPPLY
REPLACE IT.
CABLE.
EXCHANGER OBSTRUCTED;
CLEAN OR REPLACE THE EXCHANGER;
CIRCULATOR BROKEN OR
CLEAN THE IMPELLER OR REPLACE
DIRTY IMPELLER.
THE CIRCULATOR.
INCORRECT SIGNAL
IF THE MODULATION BOARD DOES NOT
RECOGNITION BY THE
RESET THE ERROR AUTOMATICALLY,
MODULATION BOARD
REPLACE IT.
MICRO-PROCESSOR.
MICRO=PROCESSOR
PARAMETERS REPROGRAMMING.
MEMORY LOSS.
FAULTY DETECTION
CLEAN IT OR REPLACE IT;
ELECTRODE;
FAULTY DETECTION
REPLACE IT;
ELECTRODE CABLE;
FAULTY MODULATION
REPLACE IT.
BOARD.
SUPPLY VOLTAGE OFF THE
CHECK THE POWER SUPPLY
OPERATION RANGE (160
NETWORK (THE ERROR DEACTIVATES
VOLTS).
AUTOMATICALLY AS SOON AS THE
SUPPLY VOLTAGE FALLS BACK WITHIN
THE REQUESTED LIMITS).
333111511 REVISION 1509.0 ECOMAX 50 SCW ES
RESET
AUTOMÁTICO.
AUTOMATIC.
AUTOMATIC.
AUTOMATIC.
MANUAL
RESET
(CUT
OFF
THE
TENSION).
MANUAL
RESET
(PRESS THE RESET
'
' KEY).
AUTOMATIC.
67