Fuel Conversion

The engine of your home generator system is factory
Calibrated and set to operate on natural gas (NG). It may also
be operated on liquefied petroleum (LP) vapor.
To configure the 8 kW fuel system for LP use:
1. Set generator's system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Remove roof and side panels.
4. Change main jet in fuel mixer following instructions
provided in LP Conversion Kit.
5. Replace side panels and roof.
6. Reinstall 15 Amp fuse in control panel.
7. Set generator's system switch to AUTO.
The system is now ready to operate automatically using
LP vapor fuel.
To configure 10 kW units with factory installed fuel
harness for LP use:
1. Press control panel "OFF" button.
2. Remove 15 Amp fuse from control panel.
3. Remove Roof.
4. Using a slotted screwdriver turn both
screws clockwise until it is snug (Over tightening can
damage mixer port)
5. Using screwdriver turn screw
and ½ turns.
D
6. Leave screw
seated.
7. Connect the fuel harness
B
solenoid
by joining the two-pin electrical
connectors.
8. Reinstall 15 Amp fuse in control panel.
9. Press control panel "AUTO" button.
10. Reinstall Roof and Close access panels.
NOTE: NG Settings from factory:
Screw C: 4 turns
Screw D: 1/2 turn
The system is now ready to operate automatically using
LP vapor fuel.
C
D
and
C
counter clockwise 2
A
to the engine
To configure 10 kW units without factory installed fuel
harness for LP use:
1. Press control panel "OFF" button.
2. Remove 15 Amp fuse from control panel.
3. Remove Roof.
4. Using a slotted screwdriver turn both
screws clockwise until it is snug (Over tightening can
damage mixer port)
5. Using screwdriver turn screw
and ½ turns.
D
6. Leave screw
seated.
7. Reinstall 15 Amp fuse in control panel.
8. Press control panel "AUTO" button.
9. Reinstall Roof and Close access panels.
NOTE: NG Settings from factory are:
Screw C: 4 turns
Screw D: 1/2 turn
A
D
C
D
and
C
counter clockwise 2
B
C
23