Refrigerant flow diagram - AQWL units
6
C
E
F
COMPONENTS
1
Tandem or trio Scroll type compressors
2
Air cooled condenser
3
Filter drier
4
Electronic expansion valve
5
Globe valve
6
Plate heat exchanger (Dual type)
7
Desuperheater (optional)
SAFETY / CONTROL DEVICES
A
High pressure switch (40.5 bar)
AT
High pressure transducer
BT
Low pressure transducer
C
Water differential pressure switch (105 mbar)
D
Air temperature sensor
E
Outlet water temperature sensor
F
Inlet water temperature sensor
G
PED pressure relief valve (45 bar)
S
5/16" shrader connection (service only)
Pipe connection with shrader valve
Note: For reasons of readability, one circuit only is shown. The second circuit is identical.
7 - Product Description (continued)
7
1
S
BT
S
EXV
CONTROL
4
VESSEL CATEGORY (≥2) / EVALUATION MODULE
2/mod. D1
2-3/mod. B+D
HAzARD CATEGORY / EVALUATION MODULE
4/mod. B+D
4/mod. H1 (4/mod. D)
A
A
S
UNIT
CONTROL
3
29
AT
G
5
2
D
5