Climatic Curves

Climatic Custom Curves

Parameters 112 and 117 set to 0 (see table 1) allows to load
in the control a custom climatic curve.
Below figures show which parameter of installer
65
55
par 4
45
35
25
15
-15
20
par 4
15
10
5
0
15
NOTE:
When NUI is installed (par 100 set to 3) or SUI Comfort mode is installed (par 100 set to 2), control is expecting the choice
between a custom or pre-set climatic curve. In case application requires fixed water set point in necessary to set an
horizontal climatic curve by setting par.120=121 for Heating Climatic Curve and 124=125 for Cooling Climatic Curve.
HEATING CLIMATIC CURVE
1
3
-10
-5
0
Outside Temperature
COOLING CLIMATIC CURVE
1
3
20
25
Outside Temperature
configuration table need to be set to create customized
heating and cooling curves.
1 - MAX W T° W1
(Parameter No 121)
2 - NO HEAT T° W1
(Parameter No 120)
3 - REGION T° O
(Parameter No 118)
4 - STOP H T° O
(Parameter No 119)
2
5
10
15
1 - MAX COOL W T° (Parameter No 125)
2 - MIN COOL W T°
(Parameter No 124)
3 - COOL STOP T°
(Parameter No 123)
4 - MAX REGION T° (Parameter No 122)
2
4
30
35
4
20
25
40
45
13