5.2

Display channels

Error code display
EC
Error code
Display range: 0, 2
0 = OK
2 = Bus error (there has been no bus communica-
tion for approx. 1 minute)
Version compatibility display
VC
Version compatibility
Display range: 0, 4
This channel indicates if the controller connected has
been recognised by the module.
If 0 is indicated, the controller has not been recog-
nised or the bus communication is faulty.
If 4 is indicated, the extension module has recognised
the controller and is functioning normally.
Display of sensor temperatures
S1 ... S6
Display of measured values
Display range: -40 ... +260 °C
Only if a sensor is connected to the corresponding
terminal, will a value be displayed.
In the case of a line break or if no sensor is connected,
9999 will be displayed.
In the case of a short circuit, 0 will be displayed.
Display of speed
R1 ... R5
Display of speed / status
Display range: 0 ... 100 %
These channels indicate the current speed values of
the relays. R5 is a potential-free relay not suitable for
speed control. Therefore, its status is indicated with
0 % or 100 % respectively.
20
Display of the software version
PG
This channel indicates the version number of the
firmware.
Display of the version number
VN
This channel indicates the version number of the
hardware.
5.3

Adjustment channels

Manual mode
M1 ... M5
Adjustment range: OFF, Auto, On
Factory setting: Auto
In the channels M1 to M5, the corresponding relays
can be switched on or off, or set to automatic mode
manually.
Manual mode
MM
Adjustment range: 0 ... 5
Factory setting: 0
The adjustment in this channel determines which re-
lays are switched on when the slide switch below the
display is set to I.
0 = Relay 1 on, all others off
1 = Relays 1 and 2 on, all others off
2 = Relays 1 and 5 on, all others off
3 = Relays 1, 2 and 5 on, all others off
4 = Relays 1 and 4 on, all others off
5 = Relays 1, 4 and 5 on, all others off
Selecting the sensor type
T1 ... T6
Adjustment range: 0 ... 4
Factory setting: 0
In this menu, a sensor type can be selected for each
sensor input. The following adjustments are available:
0 = Resistance (the measured resistance will be dis-
played independent of the sensor type connected)
1 = Pt1000
2 = KTY
3 = PT500
4 = RTA11-M (remote control)
Note
The adjustments made in the channels
T1 ... T6 only determine the display of the
measured values in the channels S1 ... S6 of
the extension module.
Î Adjust the sensor type in the controller
connected as well!
Allocating a sub-address
SA
Adjustment range: 1 ... 15
Factory setting: 1
In this channel, a sub-address can be allocated to the
module. The in- and outputs of the module will be
displayed with the sub-address number in the control-
ler connected.
Note
To register the module in the controller, use
the same number that has been selected as
sub-address! Example:
If SA = 1, register the EM as module 1 in
the controller.