English
Installation
• Make sure service has space to install connecting cables and has
easy access the unit.
Mounting & wiring
2
3
4a
/
4b 5 6 7 8
See figures
Preparation
2
1.
Take off cover
2.
Insert cable tie for KNX cable
4a
Standard mounting on standard rail TH 35-7.5
1.
Mount standard rails
2.
Attach device to standard rails from above
3.
Push down the device until it locks
4b
Screw on mounting on a level wall
Drill two holes for the screws ∅ max. 3.5 mm.
1.
2.
Tighten device and make sure it is flat (warped housings are not
permitted).
Wiring & final mounting
1.
Switch off QAX910
2.
Connect KNX cable, terminal 2: CE+, terminal 3: CE−
3.
Tighten cable tie and cut off the remainder
4.
Break out the notch from the cover
8
5.
Replace the cover
Display and operating elements
12
See figure
Page 50
LED displays
1 On
(green/red)
Dark
No power
Steady red
Web server starting (operating system)
Flashing red
Web server starting (application)
Steady green
Web server operational
2 KNX
(green)
Dark
No bus power
Lit
KNX operational
Flashing
Communication on KNX
3 Reserve
Dark
No function
4 Fault
(red)
Displays faults from the web server or the connected KNX device.
Dark
No fault
Lit
Acknowledged fault
Flashing
Unacknowledged fault
5 Addressing mode (red)
Dark
KNX addressing mode off
Lit
KNX addressing mode on
Operating buttons
The following applies when pressing the buttons
Short:
< 2 seconds
Long:
> 6 seconds
6 Remote
Short
Acknowledges fault message
Long
Sends system report to the configured receiver;
see as well "Button combination".
Siemens Building Technologies
page 2
3
.
.
5
6
7
7 Addressing mode
Short
One-time press sets the web server to the KNX ad-
dressing mode. Pressing the button again switching off
the KNX addressing mode.
Long
See "Button combination"
Button combination
and
Short
No function
Long
Reestablishes default state
Note: This resets all configuration data and settings.
The device list and all unsent messages are deleted.
History data is not deleted.
Commissioning
9 10
See figures
page 2,
Prerequisites
• The web server is mounted and wired
• The connected KNX device is commissioned
• The KNX device has a valid KNX address and is operational
• Bus power supply to the KNX bus is turned on
• Recommendation: KNX device is the clock time master on KNX
• Commissioning with a PC/laptop and a web browser via the USB
interface. The RNDIS driver must be installed to connect via USB.
Notes
• IP address USB:
192.168.250.1
IP address Ethernet:
192.168.251.1
• The RNDIS driver is automatically installed when connected via
USB when the PC/laptop is connected to the Internet.
• The RNDIS driver is supplied on the web server at
http://<IP address>/drivers/
• Additional information on commissioning is included in the detailed
Commissioning instructions C5701. It is stored on the web server at
http://< IP address>/doc/
Preparations
1.
Turn on the power to the web server. The web server is opera-
tional, when the green ON LED is lit.
2.
Plug in the supplied USB cable on the web server (connection B)
and PC. The PC recognizes the web server as a USB device.
Log onto web server
3.
Start Internet browser. In the address line, enter the USB IP ad-
dress (192.168.250.1).
4.
Login
• User name: Administrator
• Password: Password
• Click [Login] to finish
Administer user accounts
• To navigate, always start with primary navigation (upper), then use
the secondary navigation (left bar) to select the desired menu item.
• Return navigation The BACK button for the web browser used,
bread crumb navigation (path) or via primary navigation.
• Edit settings: Click the red pencil symbol .
5.
Edit administrator data:
• From the primary navigation (above), select "User accounts"
• Click red pencil symbol
• In the mask "Change user" enter:
• Password
• Repeat password
• Description (optional)
• E-mail address (optional)
• Language: English
• Click [OK] to finish
74 319 0664 0a
G5701xx
12
13
page 50,
page 51
(cannot be changed)
(default value)
08.04.2009
5 / 52